Function group "safety settings" (01)
4.1
Function "output on alarm" (010)
This function is used to select the reaction of the device on an alarm.
Selection:
•
MIN (
≤
3.6 mA)
•
MAX (22 mA)
•
hold
•
user specific
MIN (
≤
3.6 mA)
If the instrument is in alarm state, the output changes as follows:
MAX (22 mA)
If the instrument is in alarm state, the output changes as follows:
E
+
–
E
+
–
•
HART:
MIN alarm 3.6 mA (2.4 mA for 4-wire instruments)
•
PROFIBUS PA: MIN alarm -99999
•
HART:
MAX alarm 22 mA
•
PROFIBUS PA: MAX alarm +99999
3.6
(2.4)
(110
%
)
(-10
%
)
t
[mA]
22
-99999
t
HART
PROFIBUS PA
PROFIBUS PA
HART
(-10
%
)
(110
%
)
+99999