HART Multiplexer System KFD*-HM*-16
Appendix
9.4
Glossary
Address
In communication systems, an address is used to identify the device to which a message is
addressed. HART uses two addressing modes: a polling address in the range 0 to 15 and the
extended address consisting of 38 bit. The polling address 0 is reserved for 4 mA to 20 mA
analog field devices in point-to-point connections. The polling addresses 1 to 15 are reserved
for field devices in multidrop connections.
Broadcast mode
See burst mode
Burst mode
A communication mode in which the multiplexer master instructs field devices to continuously
transmit process values
–
for example, the primary variable
–
to the multiplexer master without
further instruction. The multiplexer master recognizes and supports this mode but does not put
field devices in this mode itself.
Extended address
See Address
DTM
The DTM (DTM
–
D
evice
T
ype
M
anager) contains all the data and functions of a device.
Every DTM contains its own user interface optimized for the device. The device and
communication DTMs can be integrated in any FDT frame application, such as
PACTware
.
The DTM offers almost no restriction with regard to display and user guidance. This means that
all available device functions can be operated according to the user's needs. Operation is
supported by graphics. The DTM technology enables consistent operation of a device in all
FDT systems.
Fuchs generates DTMs for HART-compatible devices by converting the
device description (DD) of these devices for use with
PACTware
.
Essentially, there are two different types of DTM:
•
Device DTMs
Device DTMs are DTMs for configuring field devices such as transmitter power supplies,
signal converters, and trip amplifiers.
•
Communication DTMs
Communication DTMs are required for communication with a device via a point-to-point
connection or via any network structures. The communication DTMs are available for
various interfaces, such as an RS-232 interface or a USB interface.
Содержание KFD Series
Страница 1: ...ISO9001 3 HART Multiplexer System KFD HM 16 PROCESS AUTOMATION MANUAL ...
Страница 41: ...HART Multiplexer System KFD HM 16 Configuration 2018 04 41 Figure 6 4 HART communication parameter window ...
Страница 46: ...2018 04 46 HART Multiplexer System KFD HM 16 Configuration Figure 6 7 General window device information ...
Страница 50: ...2018 04 50 HART Multiplexer System KFD HM 16 Configuration Figure 6 10 Command caching window ...
Страница 54: ...2018 04 54 HART Multiplexer System KFD HM 16 Configuration Figure 6 13 HART Scan wizard ...
Страница 55: ...HART Multiplexer System KFD HM 16 Configuration 2018 04 55 Figure 6 14 HART Scan Wizard communication options ...
Страница 66: ...2018 04 66 HART Multiplexer System KFD HM 16 Operation Figure 7 1 Scan loops window ...
Страница 68: ...2018 04 68 HART Multiplexer System KFD HM 16 Operation Figure 7 2 Connected field devices window ...
Страница 89: ...HART Multiplexer System KFD HM 16 Notes 2018 04 89 ...
Страница 90: ...2018 04 90 HART Multiplexer System KFD HM 16 Notes ...
Страница 91: ...HART Multiplexer System KFD HM 16 Notes 2018 04 91 ...