HART Multiplexer System KFD*-HM*-16
Configuration
201
8-04
49
6.7.4
Command Caching Function
Cyclical Data Retrieval
With cyclical data retrieval, the HART multiplexer master periodically retrieves data from the
connected field devices and stores the data in its internal memory.
If the process control system queries the data of the field devices, this data can be forwarded
more quickly. The data is no longer read directly from the field device. Instead, it is read
directly from the memory of the multiplexer master. See chapter 6.7.3.
Displaying the Command Caching Function Settings
1. Use the mouse to double-click the multiplexer master
KFD2-HMM-16
in
the project window.
2. In the editing window, open the
Configuration > Command caching
menu.
The
Command caching
window is displayed.
3. Click
Apply
to confirm your selection.
4. Select
Revert
to reset your selection.
The command parameters for the multiplexer master are displayed and set in the
Command caching
menu:
•
Mode
: This switches the
Command caching
function on or off.
•
Disabled
: The function is switched off.
•
Default caching
: The function is switched on. This is the default setting.
The commands selected are cached, see below.
•
HART command
: Here you can use a drop-down menu to select which values are to
be read out from the field devices:
•
Command 1 - Read Primary Variable
: Only the primary variable of the field device
is read out.
•
Command 2 - Read Loop Current and Percent Of Range
: The current value in mA
is read out.
•
Command 3 - Read Dynamic Variables and Loop Current
: All variables of
the field device are read out.
Содержание KFD Series
Страница 1: ...ISO9001 3 HART Multiplexer System KFD HM 16 PROCESS AUTOMATION MANUAL ...
Страница 41: ...HART Multiplexer System KFD HM 16 Configuration 2018 04 41 Figure 6 4 HART communication parameter window ...
Страница 46: ...2018 04 46 HART Multiplexer System KFD HM 16 Configuration Figure 6 7 General window device information ...
Страница 50: ...2018 04 50 HART Multiplexer System KFD HM 16 Configuration Figure 6 10 Command caching window ...
Страница 54: ...2018 04 54 HART Multiplexer System KFD HM 16 Configuration Figure 6 13 HART Scan wizard ...
Страница 55: ...HART Multiplexer System KFD HM 16 Configuration 2018 04 55 Figure 6 14 HART Scan Wizard communication options ...
Страница 66: ...2018 04 66 HART Multiplexer System KFD HM 16 Operation Figure 7 1 Scan loops window ...
Страница 68: ...2018 04 68 HART Multiplexer System KFD HM 16 Operation Figure 7 2 Connected field devices window ...
Страница 89: ...HART Multiplexer System KFD HM 16 Notes 2018 04 89 ...
Страница 90: ...2018 04 90 HART Multiplexer System KFD HM 16 Notes ...
Страница 91: ...HART Multiplexer System KFD HM 16 Notes 2018 04 91 ...