O
PERATING
S
OFTWARE
OS6.0
/
OS10.0
41
PRESELECTION 5
Preselection / switch point 5
Value
Function
-99999999
Smallest preselection value
5000
Default value
99999999
Largest preselection value
PRESELECTION 6
Preselection / switch point 6
Value
Function
-99999999
Smallest preselection value
6000
Default value
99999999
Largest preselection value
4.7
Preselection 1 Menu
MODE 1
Switch condition for preselection 1. Output switches according to the following
condition:
Value Designation
Function
0
|RESULT|>=|PRES|
Amount of measurement result greater than or
equal to amount of PRESELECTION 1
With HYSTERESIS 1 not equal to 0, the
following switch condition results:
Measurement result >= PRESELECTION 1
ON,
Measurement result < PRESELECTION 1 –
HYSTERESIS 1
OFF
1
|RESULT|<=|PRES| Amount of measurement result less than or
equal to amount of PRESELECTION 1
(Startup override STARTUP DELAY
recommended)
With HYSTERESIS 1 not equal to 0, the
following switch condition results:
Measurement result <= PRESELECTION 1
ON,
Measurement result > PRESELECTION 1+
HYSTERESIS 1
OFF
Содержание K23-SSI/Rx/IU-C
Страница 1: ...Your automation our passion K23 SSI Rx IU C Signal converter Manual...
Страница 77: ...APPENDIX 77 5 6 Reading in the SSI Value The received data is always filled internally to a 32 bit data length...
Страница 79: ...APPENDIX 79 Calculating the SSI Zero Position Checking the direction of rotation Evaluating the bit suppression...
Страница 80: ...APPENDIX 80 Calculating the SSI offset Calculating the display value...
Страница 83: ...APPENDIX 83 5 8 Dimensions...
Страница 84: ...www pepperl fuchs com Subject to modifications Pepperl Fuchs Printed in Germany DOCT 6641...