ICE1-*-G60L-V1D, ICE1-*-G60L-C1-V1D
Commissioning for EtherCAT
•
Each physical input bit to be transfered to the EtherCAT
®
controller can be assigned to
your preferred bit position in the input data frame. The available settings are 0 ... 7, 0 ... 15
(0 = X1A ... 15 = X8B), or 255 for the inactive setting.
•
For I/O channels that are configured as "input/output,
”
the mapping configuration applies
to the input direction (producing data) and output direction (consuming data).
The appropriate settings are preconfigured for each profile (16DI/DO, 16DI, 16DO, 8DI/DO,
8DI, 8DO, 8DI/8DO). This means that it is not necessary to adjust these parameters for most
applications.
Possible I/O Mapping Configuration
The following table provides an overview of the relationship between the preconfigured I/O port
channel (X1A... X8B) and the I/O process data channel (0 ... 15) for each profile.
Standard I/O Mapping Configuration
Example of process data in the
byte
format:
Index
(byte?)
Parameter
0x2304:01
I/O mapping configuration port X1A: 0 ... 15 = process data channel 0 ... 15, 255
= inactive
0x2304:02
I/O mapping configuration port X1B: 0 ... 15 = process data channel 0 ... 15, 255
= inactive
...
...
0x2304:0F
I/O mapping configuration port X8A: 0 ... 15 = process data channel 0 ... 15, 255
= inactive
0x2304:10
I/O mapping configuration port X8B: 0 ... 15 = process data channel 0 ... 15, 255
= inactive
Table 7.52
I/O process data channel (0 ... 15), 255 = inactive/not available
Index
(byte)
Port
16DI/DO 16DI
16DO
8DI/DO
8DI
8DO
8DI/8DO
0x2304:01 X1A
0
0
0
0
0
0
0
0x2304:02 X1B
1
1
1
255
255
255
1
0x2304:03 X2A
2
2
2
1
1
1
2
0x2304:04 X2B
3
3
3
255
255
255
3
0x2304:05 X3A
4
4
4
2
2
2
4
0x2304:06 X3B
5
5
5
255
255
255
5
0x2304:07 X4A
6
6
6
3
3
3
6
0x2304:08 X4B
7
7
7
255
255
255
7
0x2304:09 X5A
8
8
8
4
4
4
0
0x2304:0A X5B
9
9
9
255
255
255
1
0x2304:0B X6A
10
10
10
5
5
5
2
0x2304:0C X6B
11
11
11
255
255
255
3
0x2304:0D X7A
12
12
12
6
6
6
4
0x2304:0E X7B
13
13
13
255
255
255
5
0x2304:0F X8A
14
14
14
7
7
7
6
0x2304:10 X8B
15
15
15
255
255
255
7
Table 7.53