ICE1-*-G60L-V1D, ICE1-*-G60L-C1-V1D
Commissioning for EtherNet/IP
2
0
1
9
-1
0
19
5
Commissioning for EtherNet/IP
5.1
Preparation
To configure a module in the controller, you need an EDS file. Each of the module variants
requires its own EDS file.
Downloading the EDS File
You can find the relevant EDS file in the
Software
section of the product detail page for the
device.
Use the hardware or network configuration tools from your controller manufacturer to install the
EDS file for the module variant used. After installation, the modules can be found in the hard-
ware catalog as "General Purpose Discrete I/O" devices.
Reading MAC IDs
Each module has a unique, manufacturer-assigned MAC ID that cannot be changed by the
user. The assigned MAC ID is printed on the right-hand side of the module.
Setting the Network Parameters
Using the three control switches on the front of the modules, you can set the operating mode
for receiving network parameters such as the IP address, subnet mask, and gateway address.
Please note that a fixed IP address is required to use QuickConnect.
Once the power supply has been restored, the modules read in the switch positions. The
selected operating mode overwrites the saved settings.
The devices support the DHCP and BOOTP protocols for receiving the required network
parameters such as IP address and subnet mask.
The factory settings of the static network parameters are:
•
IP address: 192.168.001.001
•
Subnet mask: 255.255.255.000
•
Gateway address: 000.000.000.000
The following settings are possible via the rotary coding switches:
Rotary switch posi-
tion
Function
000
(As delivered)
The DHCP and BOOTP functionality is activated as standard on deliv-
ery. The network parameters are initially requested using DHCP
requests. If this is not successful, the request is made using BOOTP
requests. The network parameters are not saved; however, it is possi-
ble to save them via the integrated web server.
000
(Network parameters
already saved)
The last-saved network parameters are used (IP address, subnet
mask, gateway address, DHCP on/off , BOOTP on/off).
001 to 254
The last three digits of the saved or default IP address are overwritten
by the control switch setting.
255 to 298
(Default: 299)
The network parameters are requested via DHCP and BOOTP but are
not saved.