2
0
2
1
-0
2
14
Installation
3
Installation
3.1
Storage and Transportation
Keep the original packaging. Always store and transport the device in the original packaging.
Store the device in a clean and dry environment. The permitted ambient conditions must be
considered, see datasheet.
3.2
Unpacking
Check the product for damage while unpacking. In the event of damage to the product, inform
the post office or parcel service and notify the supplier.
Retain the original packaging in case the device must be stored or shipped again at a later
date.
Should you have any questions, please contact Fuchs.
3.3
Mounting
Mount the device with both brackets (1) on a solid, continuous surface.
Figure 3.1
Mounting brackets (1)
3.4
Connecting the Auxiliary Current Flat Cable
The motor control module is connected to the PWR auxiliary voltage supply via the black flat
cable. The permissible auxiliary voltage is 18 V to 30 V.
The contact between the motor control module and flat cables is established via two metal
piercing pins and uses insulation piercing technology. The flat cable is routed through a cable
guide with hinges. When closed, the cable guide is locked by a locking bracket and can be
opened again without tools.
Flat-profile cables are narrow on top (with visibly offset profile edge) and wide underneath (pro-
file edge not visible). The cable guide allows the flat cables to be inserted on either side,
enabling flat cables that are already laid in cable ducts to be connected flexibly. However, it is
important to ensure that the profile edge always points toward the motor control module. The
mechanical reverse polarity protection prevents the cable guide from closing completely if the
flat cable is inserted incorrectly.
1
Caution!
If a flat cable is inserted incorrectly, the motor control module will not work.
If the flat cable is inserted in the cable guide in the wrong direction, the voltage is inverted. The
motor control module will not work. However, the internal electrical reverse polarity protection
protects it from damage.
Table 3.1 ICA-8DIO4M1-G20-IO