2
0
2
1
-0
2
24
IO-Link Parameters
Motor 4 Control Configuration
75
(0x4B)
MCC4 Con-
fig
r/w
Record (1) 5 byte
Configuration parameters of the
motor control channel MCC4.
.1
Output
mode
UInteger
(8)
32
0: digital output
1: motor con-
trol
0
Output mode as motor control or
digital output.
.2
Output logic
UInteger
(8)
24
0: high active
-
not inverted
1: low active
-
inverted
0
Output logic for the digital output.
.3
Error logic
UInteger
(8)
16
0: high active
-
not inverted
1: low active
-
inverted
0
Logic of the fault signal input.
.4
Speed
range min
UInteger
(8)
8
0 ... 136
20
Voltage level for the minimum
speed in 0.1 V increments.
.5
Speed
range max
UInteger
(8)
0
0 ... 136
100 Voltage level for the maximum
speed in 0.1 V increments.
Motor 1 Configuration of the Maintenance Requirement
80
(0x50)
MCC1 Con-
figMReq
r/w
Record (1) 12 byte
Configuration parameters for the
maintenance requirement prop-
erties of the motor control chan-
nel MCC1
.1
Runtime
interval
UInteger
(32)
64
0: deactivated
1 ... 1000000
0
Motor runtime interval for a main-
tenance requirement warning in
hours
.2
Run cycle
interval
UInteger
(32)
32
0: deactivated
1 ...
4294967295
0
Motor run cycle interval for a
maintenance requirement warn-
ing
.3
Error count
interval
UInteger
(32)
0
0: deactivated
1 ...
4294967295
0
Motor fault count interval for a
maintenance requirement warn-
ing
Motor 2 Configuration of the Maintenance Requirement
81
(0x51)
MCC2 Con-
figMReq
r/w
Record (1) 12 byte
Configuration parameters for the
maintenance requirement prop-
erties of the motor control chan-
nel MCC2
.1
Runtime
interval
UInteger
(32)
64
0: deactivated
1 ... 1000000
0
Motor runtime interval for a main-
tenance requirement warning in
hours
.2
Run cycle
interval
UInteger
(32)
32
0: deactivated
1 ...
4294967295
0
Motor run cycle interval for a
maintenance requirement warn-
ing
.3
Error count
interval
UInteger
(32)
0
0: deactivated
1 ...
4294967295
0
Motor fault count interval for a
maintenance requirement warn-
ing
Motor 3 Configuration of the Maintenance Requirement
82
(0x52)
MCC3 Con-
figMReq
r/w
Record (1) 12 byte
Configuration parameters for the
maintenance requirement prop-
erties of the motor control chan-
nel MCC3
Index/
.sub
Parameter
Acc
ess Data Type Length
Bit
Off-
set Value Range
Def
ault Description