![Pepperl+Fuchs HiC283 Series Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/pepperl-fuchs/hic283-series/hic283-series_manual_1527593009.webp)
Functional Safety HiC283*
Product Description
20
21
-1
2
9
2.2
Interfaces
The device has the following interfaces:
•
Safety relevant interfaces:
•
1-channel devices: input I, output I, output II (optional)
•
2-channel devices: input I, input II, output I, output II
•
Non-safety relevant interfaces: power supply, fault output
2.3
Marking
2.4
Standards and Directives for Functional Safety
Device-specific standards and directives
System-specific standards and directives
Note
For corresponding connections see datasheet.
Fuchs Group
Lilienthalstraße 200, 68307 Mannheim, Germany
Internet: www.pepperl-fuchs.com
HiC2831, HiC2832, HiC2831R1, HiC2832R1
HiC2831R2, HiC2832R2, HiC2831R3, HiC2832R3
HiC2831R4, HiC2832R4, HiC2831R5, HiC2832R5
Up to SIL 2
Note
If you design the safety loops in homogeneous redundancy (HFT = 1), you can use the devices
in applications up to SIL 3.
Functional safety
IEC/EN 61508, part 2, edition 2010:
Functional safety of electrical/electronic/programmable electronic
safety-related systems (manufacturer)
Functional safety
IEC 61511-1:2016+COR1:2016+A1:2017
EN 61511-1:2017+A1:2017
Functional safety
–
Safety instrumented systems for the process
industry sector (user)