Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282*
Planning
2
014-
09
7
2.2
Assumptions
The following assumptions have been made during the FMEDA analysis:
Only one input and one output are part of the considered safety function
(only 2-channel version).
The device shall claim less than 10 % of the total failure budget for a SIL2
safety loop.
For a SIL2 application operating in Low Demand Mode the total PFD
avg
value
of the SIF (
S
afety
I
nstrumented
F
unction) should be smaller than 10
-2
, hence
the maximum allowable PFD
avg
value would then be 10
-3
.
For a SIL2 application operating in High Demand Mode of operation the total
PFH value of the SIF should be smaller than 10
-6
per hour, hence the
maximum allowable PFH value would then be 10
-7
per hour.
Failure rate based on the Siemens SN29500 data base.
Failure rates are constant, wear out mechanisms are not included.
External power supply failure rates are not included.
The safety-related device is considered to be of type
A
components with a
Hardware Fault Tolerance of
0
.
Since the loop has a Hardware Fault Tolerance of
0
and it is a type
A
component, the SFF must be > 60 % according to table 2 of IEC 61508-2 for a
SIL2 (sub)system.
It is assumed that the device will be used under average industrial ambient
conditions, which are comparable with the classification "stationary mounted"
in MIL-HDBK-217F. Alternatively, the following ambient conditions are
assumed:
• IEC 60654-1 Class C (sheltered location) with temperature limits in the
range of the manufacturer's specifications and an average temperature
of 40
º
C over a long period. A moisture level within the manufacturer's
specifications is assumed. For a higher average temperature of 60
º
C,
the failure rates must be multiplied by a factor of 2.5 based on empirical
values. A similar multiplier must be used if frequent temperature
fluctuations are expected.
It is assumed that any safe failures that occur (e.g., output in safe condition)
will be corrected within eight hours (e.g., correction of a sensor fault).
While the device is being repaired, measures must be taken to maintain the
safety function (e.g., by using a replacement device).
The indication of a dangerous fault (via fault bus) is detected within 1 hour by
the programmable logic controller (PLC).
Содержание HiC2821
Страница 1: ...ISO9001 2 Switch Amplifier KCD2 SR Ex LB SP HiC282 PROCESS AUTOMATION SAFETY MANUAL SIL ...
Страница 17: ...Safety Manual SIL KCD2 SR Ex LB SP HiC282 Notes 2014 09 17 Safety Manual SIL KCD2 SR Ex LB HiC282 ...
Страница 18: ...2014 09 18 Safety Manual SIL KCD2 SR Ex LB SP HiC282 Notes ...
Страница 19: ...Safety Manual SIL KCD2 SR Ex LB SP HiC282 Notes 2014 09 19 ...