Product Description
2
02
0-
11
23
3.2.3
Mounting the Stand-Alone Kit and the Advanced Diagnostic Module
For mounting the HD2-DM-A diagnostic module, see chapter 3.1.4.
Indicators/operating means
LED PRI PWR
green: on, primary bulk power supply con
-
nected
LED SEC PWR
green: on, secondary bulk power supply con
-
nected
LED Seg 1...4
yellow: bus activity; red 2 Hz flashing: alarm;
red: hardware error
Fault signal
VFC alarm 1 A, 50 V DC, normally closed
DIP-switch
diagnostic address 1...247, binary coded
Interface
Interface type
diagnostic bus: RS 485
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC
EN 61326-1:2006
Standard conformity
Electromagnetic compatibility
NE 21
Degree of protection
IEC 60529
Shock resistance
EN 60068-2-27
Vibration resistance
EN 60068-2-6
Ambient conditions
Ambient temperature
-40 ... 60
°
C (-40 ... 140
°
F)
Storage temperature
-40 ... 85
°
C (-40 ... 185
°
F)
Relative humidity
< 95 % non-condensing
Shock resistance
15 g 11 ms
Vibration resistance
1 g , 10 ... 150 Hz
Mechanical specifications
Connection type
screw terminals
Core cross-section
2.5 mm
2
Housing material
Polycarbonate
Housing width
50 mm
Housing height
220 mm
Housing depth
162 mm
Degree of protection
IP20
Mass
approx. 290 g
Mounting
DIN mounting rail
International approvals
FM approval
CoC 3024816, CoC 3024816C
Approved for
Class I, Division 2, Groups A, B, C, D, T4 /
Class I, Zone 2, AEx/Ex nA IIC T4
Содержание HD2-DM-A
Страница 1: ... Advanced Diagnostics HD2 DM A KT MB DMA KT MB GT2AD FF KT MB GT2AD FF IO Manual ...
Страница 131: ...Advanced Diagnostics FOUNDATION Fieldbus Integration 2020 11 131 ...
Страница 133: ...Advanced Diagnostics FOUNDATION Fieldbus Integration 2020 11 133 3 Select Browse The Device Selection window appears ...
Страница 136: ...2020 11 136 Advanced Diagnostics FOUNDATION Fieldbus Integration ...