PACTware Multi-Input/Output Device Type Manager
2
0
1
8
-0
7
79
Section "Batch":
■
Batch ID:
Identification assignment option.
Free value field, assign an identifier for a batch process with distributed fieldbus systems
to enhance process identification.
■
Unit
Free value field, assign an identifier for a batch unit with distributed fieldbus systems to
enhance process identification. Example: Enter number of recipe unit procedure or of
unit.
■
Operation
Free value field, assign an identifier for a batch operation with distributed fieldbus systems
to enhance process identification. Example: Enter number of recipe operation.
■
Phase
Free value field, assign an identifier for a phase with distributed fieldbus systems to
enhance process identification. Example: Enter number of a recipe phase.
Adjusting the General Settings
1. Use the different fields to enter the information you require for your process.
2. Click on
Apply
to confirm.
10.3.5
Tab "Process Data" for a Binary Input
This tab contains all settings and parameters for the binary input of the channel and the fail-
safe settings.
Figure 10.17
Channel "Process Data" tab for the binary input
The tab "Process data" contains the following channel information and parameters: