Advanced Diagnostics for AS-i Masters
The advanced AS-i diagnostics is intended to localize occasionally occurring con-
figuration errors and to determine the quality of data transmission on AS-i without
using additional diagnostics tools.
AS-i Control Tools, a MS-Windows software designed to simplify AS-i installation
and used to program AS-i Control, enables operation of the advanced diagnostics
functions (LCS, error counters, and LOS).
11.1
List of corrupted AS-i Slaves (LCS)
The
LCS
contains the information from the list of slaves with configuration error
(
Delta list
). In addition to the list of configured slaves (
LPS
), the list of detected
slaves (
LDS
), and the list of activated slaves (
LAS
), the AS-i master creates a
fourth list, the list of corrupted slaves (
LCS
) containing advanced diagnostics
data used to diagnose the causes for intermittently occurring configuration errors
on AS-i. This list contains entries for all AS-i slaves that were responsible for at
least one intermittent configuration error since the list was last read or since the
AS-i master was turned on. Furthermore, intermittent AS-i power failures are list-
ed in the
LCS
at the position of AS-i slave with address ’0’.
11.2
Protocol analysis: Counters for corrupted data telegrams
The AS-i master with advanced diagnostics provides a counter for telegram repe-
titions for each AS-i slave. The counter counts up every time a corrupted data tel-
egram has been found, making it possible to determine the quality of the trans-
mission if only a few telegrams are corrupt and the AS-i slave never caused a
configuration error.
Displaying the protocol analysis is possible through the AS-i Control Tools soft-
ware by using the command "Master | AS-i Diagnostics".
Information!
Whenever the LCS is read it is deleted from memory.
Information!
The last intermittent configuration error can also be displayed on the AS-i master:
Pressing the "Set" button on the AS-i master initiates the display of the AS-i slave
responsible for the last intermittent configuration error. If a intermittent AS-i power fail-
ure occurred, the display shows 39 after pressing the "Set" button.
This function is only available if the device is in normal operating mode of the protected
mode (display empty) or in the off-line phase (Display: "40").
Information!
The counter values are read via the host interface and will be deleted after they were
read.