AS-i 3.0 Command Interface
Commands of the Command Interface
Monitor state
Code
significance
0
protective mode, everything OK (output circuits that are not installed, not con-
figured or dependent output circuits are indicated as OK)
1
protective mode, output circuit 1 off.
2
protective mode, output circuit 2 off
3
protective mode, both output circuits off.
4
configuration mode: power on
5
configuration mode
6
reserved / not defined
7
configuration mode: fatal device error, RESET or device replacement neces-
sary
Tab. 4-47.
Color coding
Code
color
meanining
0
green
block is in the ON state (switched on)
1
green flashing
block is in the ON state (switched on), but already in the
transition to the OFF state, e.g. shutdown delay
2
yellow
block is ready, but is still waiting for a further condition, e.g.
local acknowledgement or Start button
3
yellow flashing
time condition exceeded, action must be repeated, e.g. syn-
chronization time exceeded
4
red
block is in the OFF state (switched off)
5
red flashing
the error interlock is active, clear using one the following
actions:
> Acknowledge using the ESC/Service button
> Power OFF/ON
> AS-i OFF/ON
6
grey
OSSD not used / no communication with the AS-i slave
Tab. 4-48.
Information!
See also the separate "Safety-at-Work" monitor documentation for a description of the
codes used for monitor state, OSSD state, device colors and assignments to OSSDs.