Is
s
u
e
d
a
te
:
7
.6
.2
0
1
3
54
AS-i 3.0 Command Interface
Commands of the Command Interface
4.4.8
Get list of peripheral faults (GET_LPF)
With this call, the list of peripheral faults (
LPF
) signaled by the AS-i slaves is read
out from the AS-i master. The LPF is updated cyclically by the AS-i master. If and
when an AS-i slave signals faults of the attached peripherals (for example broken
wire) can be found in the description of the AS-i slave.
Request
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
3E
16
2
T
O
circuit
Tab. 4-87.
Response (if O
≡
0)
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
3E
16
2
T
result
3
7A
6A
5A
4A
3A
2A
1A
0A
…
…
10
31B
30B
29B
28B
27B
26B
25B
24B
Tab. 4-88.
Response (if O
≡
1)
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
3E
16
2
T
result
3
0A
1A
2A
3A
4A
5A
6A
7A
…
…
10
24B
25B
26B
27B
28B
29B
30B
31B
Tab. 4-89.
Содержание AS-I 3.0
Страница 1: ...AS I 3 0 COMMAND INTERFACE FACTORY AUTOMATION MANUAL...
Страница 177: ......