AS-i 3.0 Command Interface
Command Interface Examples
4. Wait until master is in normal operation mode (and protected mode).
Reading out the flags until NA (Normal Operation Active) has been set.
No result because toggle bit = 0.
Setting the toggle bit:
The flag NA has to be set before the application is started. In case it is not set, the
flags have to be read out until this flag has been set to 1.
request: GET_FLAGS
byte 1
47
hex
(GET_FLAGS)
byte 2
00
hex
(T = 0, master 1, single master)
byte 3
00
hex
…
…
byte 12
00
hex
Tab. 5-307.
Response
byte 1
00
hex
(or old values)
byte 2
00
hex
(or old values)
…
…
byte 12
00
hex
(or old values)
Tab. 5-308.
request: GET_FLAGS
byte 1
47
hex
(GET_FLAGS)
byte 2
00
hex
(T = 0, master 1, single master)
byte 3
00
hex
byte 4
00
hex
…
…
byte 12
00
hex
Tab. 5-309.
response
byte 1
47
hex
byte 2
80
hex
(T = 1, result = 0)
byte 3
-
-
-
-
-
-
-
POK
byte 4
OR
APF
NA
CA
AAv
AAs
S0
COK
byte 5
AAe
OL
DX
byte 6
00
hex
…
byte 12
00
hex
Tab. 5-310.