AS-i 3.0 Command Interface
Command Interface Examples
12-byte management
1. Switch master to config mode.
No result because toggle bit = 0.
Set the toggle bit:
Master is now in configuration mode.
Result = 0
⇒
No error, for other result codes see chap. <Commands of the Com-
request: SET_OP_MODE
byte 1
0C
hex
(SET_OP_MODE)
byte 2
00
hex
(T = 0, master 1, single master)
byte 3
01
hex
(= config mode)
byte 4
00
hex
…
…
byte 12
00
hex
Tab. 5-295.
Response
byte 1
00
hex
(or old values)
byte 2
00
hex
(or old values)
…
…
byte 12
00
hex
(or old values)
Tab. 5-296.
request: SET_OP_MODE
byte 1
0C
hex
(SET_OP_MODE)
byte 2
80
hex
(T = 1, master 1, single master)
byte 3
01
hex
(= config mode)
byte 4
00
hex
…
…
byte 12
00
hex
Tab. 5-297.
Response
byte 1
0C
hex
byte 2
80
hex
(T = 1, result = 0)
byte 3
00
hex
(or old values)
…
…
byte 12
00
hex
(or old values)
Tab. 5-298.