AS-i 3.0 Command Interface
Commands of the Command Interface
Channels 1 and 2 describe the states of the respective OSSDs of the monitor.
Channel 3 describes if warnings or disturbances occured in one or more devices
assigned this OSSD. This means:
Binary data
UA
UAS-i
AS-i voltage is sufficient
1: AS-i voltage is sufficient
0: AS-i voltage is
not
sufficient
AU
AUX 24 V
24 V for safe outputs supply is present
1: 24 V for safe outputs supply is present
0: 24 V for safe outputs supply is
not
present
Coding of the OSSD’s state
Code bit
[3 ... 0]
Status resp. color
Description
0
Green continuous
Output on
1
Green flashing
Delay time is running at stop category 1
2
Yellow continuous
Start-up/restart-disable active
3
Yellow flashing
External test necessary / acknowledgement /
start delay active
4
Red continuous
Output off
5
Red flashing
Error
6
Grey resp. off
Output not projected
Tab. 4-273.
YF
yellow flashing
At least one of devices assigned to this OSSD is in the state
yellow flashing.
RF
red flashing
At least one of devices assigned to this OSSD is in the state
red flashing.
D3
D2
D1
D0
monitor -
> master
(input)
serial commu-
nication
serial commu-
nication
1: output ’2’ is
switched off or
green flashing
1: output ’1’ is
switched off or
green flashing
master -
> monitor
(output)
change from ’0’
to ’1’ resets the
error-traffic
light AS-i 2
change from ’0’
to ’1’ resets the
error-traffic
light AS-i 1
serial
communication
serial
communication
Tab. 4-274.
Information!
Additional information on diagnostics via Profile S-7.5.5 can be found in system man-
ual "AS-i 3.0 PROFIBUS Gateways with integr. safety monitor".