AS-i 3.0 Command Interface
Commands of the Command Interface
Transparent input data
Channel ’0’ of the transparent input data describes the state of both AS-i circuits.
The upper 8 bits describe the state of AS-i circuit 2, the lower the state of AS-i
circuit 1.
Channels 1 and 2 contain the colors of release circuits (currently only 2 colors are
supported).
Finally the summary information appear on device colors of the release circuits in
channel 3.
All items are described as follows:
channel
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
0
AS-i circuit 2
AU
RT
GE
GN
UA
DA
EF
1
state OSSD 4
state OSSD 3
2
state OSSD 8
state OSSD 7
3
OSSD8
OSSD7
OSSD6
OSSD5
RF
YF
RF
YF
RF
YF
RF
YF
Tab. 4-271.
channel
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
0
AS-i circuit 1
RT
GE
GN
UA
DA
EF
1
state OSSD 2
state OSSD 1
2
state OSSD 6
state OSSD 5
3
OSSD4
OSSD3
OSSD2
OSSD1
RF
YF
RF
YF
RF
YF
RF
YF
Tab. 4-272.
EF
earth fault
Earth fault is present
1: earth fault is present
0: earth fault is
not
present
DA
duplicate
address
Duplicate address is present
1: duplicate address on AS-i
0:
no
duplicate address on AS-i
GN
green
Error free or almost error free communication
< 1% telegram repetitions
GE
warning
More frequent repetitions, which should be clarified depending upon applica-
tion
1% - 5% telegram repetitions
RT
error
Fatal disturbances
> 5% telegram repetitions