AS-i 3.0 Command Interface
Commands of the Command Interface
4.8.7
Replacement of Safety Slaves input data
(Function 0F
16
)
Use this function to replace safety slaves input data with "interpretation data". If
the function is active, so have safety slaves input data the following meaning:
Bit 0, 1: 00=channel 1 has released, 11=channel 1 has not released.
Bit 2, 3: 00=channel 2 has released, 11=channel 2 has not released.
Set:
Read:
Information!
This command replaces the old command MB_FP_LSS_ENABLE.
Request
Byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
7D
16
2
T
–
circuit
3
0F
16
4
safety slaves
1
1.
Value: 0= no substitute value, 1=substitute value for safety slaves.
Tab. 4-240.
Response
Byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
7D
16
2
T
result
Tab. 4-241.
Request
Byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
7E
16
2
T
–
circuit
3
0F
16
Tab. 4-242.
Response
Byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
7E
16
2
T
result
4
safety slaves
1
1.
Value: 0= no substitute value, 1=substitute value for safety slaves.
Tab. 4-243.