5.8. Calendar
override
setting
The controller needs a method to set days between regeneration for regulatory requirements and in
cases when the flow sensor has failed.
5.9. System
selection
The controller has four system settings available. The system selections accommodate multiple tank
sizes and various feedwater conditions.
System selection:
5.10. Regeneration cycles time
A
Press and hold
and
for 3 seconds.
→ The programmed calendar override is displayed.
B
Press
to increases value.
→ Range from 0 through 30;
0 = Disabled;
0.3 = Regeneration every 8 hours : at 2, 10 and 18 hours;
0.5 = Regeneration every 12 hours : at 2 and 14 hours;
1 - 30 = Regeneration every X days (every 3 days in this
example).
A
Press and hold
and
simultaneously for 3 seconds.
→ A small "u" will be displayed in the left digit.
→ The right digit will display the current system setting.
B
Press
until desired system setting appears then release.
→ The displayed system setting will be stored in flash memory
when the controller exits programming after 5 seconds.
C#
Cycle
Resin bed
flow
direction
System u# [minutes]
u1
u2
u3
u4
C1
Backwash
↑
8
8
1
3
C2
Brine draw
↓
Calculated
Calculated
Calculated
Calculated
Slow rinse
25
45
25
45
C3
Repressurize
None
3
3
3
3
C4
Rapid rinse
↓
3
3
1
3
C5
2nd backwash
↑
1
1
1
1
C6
2nd rapid rinse
↓
1
1
1
1
C7
Brine refill
None
Calculated
Calculated
Calculated
Calculated
Содержание Riversoft
Страница 1: ...Riversoft Water Softener INSTALLER MANUAL WATER PURIFICATION...
Страница 61: ...Installer Manual Riversoft Maintenance Ref MKT IM 045 A 13 03 2020 61 90...
Страница 65: ...Installer Manual Riversoft Maintenance Ref MKT IM 045 A 13 03 2020 65 90...
Страница 73: ...Installer Manual Riversoft Maintenance Ref MKT IM 045 A 13 03 2020 73 90 PAGE INTENTIONALLY LEFT BLANK...
Страница 75: ...Installer Manual Riversoft Maintenance Ref MKT IM 045 A 13 03 2020 75 90...
Страница 77: ...Installer Manual Riversoft Maintenance Ref MKT IM 045 A 13 03 2020 77 90 turn turn Point 0 Point 0...
Страница 89: ...Installer Manual Riversoft Disposal Ref MKT IM 045 A 13 03 2020 89 90 PAGE INTENTIONALLY LEFT BLANK...
Страница 90: ...www pentairaquaeurope com...