background image

 
 
 
 
 
 
 
 
 
 

 

 
 

INSTRUCTION MANUAL FOR: 

 

T15 AIR CONDITIONER

 

 

McLean Thermal 
11611 Business Park Blvd. N   Champlin, MN 55316 
Tel: 763-323-8200   Fax: 763-576-3200 

 
www.mcleanthermal.com

 

87922502

Содержание McLean Thermal T Series

Страница 1: ...INSTRUCTION MANUAL FOR T15 AIR CONDITIONER McLean Thermal 11611 Business Park Blvd N Champlin MN 55316 Tel 763 323 8200 Fax 763 576 3200 www mcleanthermal com 87922502 ...

Страница 2: ...on and packing material and request an inspection Then file a claim with the delivering carrier McLean Thermal cannot accept responsibility for freight damages however we will assist you in any way possible HANDLING TESTING THE AIR CONDITIONER If it is necessary to place the air conditioner in a horizontal position after unpacking be certain it is placed in an upright vertical or mounting position...

Страница 3: ...will continue to operate and the compressor will restart after it has cooled to within the thermal overload cut in temperature setting INSTALLATION Step 1 Inspect air conditioner Verify functionality before mounting the air conditioner see Handling Testing the Air Conditioner on page 1 Step 2 Using the cutout dimensions shown in this manual prepare the air IN and air OUT openings and mounting bolt...

Страница 4: ...oltage Hz Amps Phase Temp o F o C Lbs Kgs T15 0116 GXXX 115 60 3 6 1 800 131 55 27 12 3 T15 0116 GXXX 100 50 3 8 1 800 125 52 27 12 3 T15 0126 GXXX 230 60 1 5 1 900 131 55 27 12 3 T15 0126 GXXX 220 50 1 4 1 800 125 52 27 12 3 XXX will be replaced with a three digit number designating all desired options Consult the factory for specific model numbers T15 Model Drawing ...

Страница 5: ...10 Coil Condenser 15 1001 02 15 1001 02 Coil Condenser Coated 15 1001 01 15 1001 01 Coil Evaporator 15 1001 03 15 1001 03 Compressor 10 1016 82 10 1026 101 Filter Air Reusable 10 1000 91 10 1000 91 Filter Dryer 52 6028 03 52 6028 03 Freeze stat 10 1033 26 10 1033 26 Service Cord 52 6035 138 52 6035 139 Terminal Block 10 1003 03 10 1003 03 Thermal Overload Compressor 10 1007 67 10 1007 68 Thermosta...

Страница 6: ...10 1008 194 Rev 2 Page 5 T15 Wire Diagram T15 Schematic ...

Страница 7: ...t is hermetically sealed properly lubricated at the factory and should provide years of satisfactory operating service Should the refrigerant charge be lost recharging ports access fittings on the suction and discharge sides of the compressor are provided for recharging and or checking suction and discharge pressures Under no circumstances should the access fitting covers be loosened removed or ta...

Страница 8: ...asis The inlet air filter is located behind the front cover To access filter pull ring protruding from slot in bottom of front cover The filter may now be cleaned or new filter installed Cleaning Instructions 1 Flush the filter with warm water from the exhaust side to the intake side DO NOT USE CAUSTICS 2 After flushing allow filter to drain Placing it with a corner down will assure complete drain...

Страница 9: ...NO possible Defective thermostat Open motor winding Stuck fan motor Obstructed blades 6 Carefully check the compressor for operation motor should cause slight vibration and the outer case of the compressor should be warm YES wait 5 minutes then proceed to step 7 NO possible Defective thermostat Defective capacitor Defective overload Defective relay 7 Make sure the coils are clean Then check evapor...

Страница 10: ... t run Low line voltage at start Should be 10 rated voltage Compressor motor stuck Bad contactor Bad overload switch Bad run start capacitor Unit blows breakers Under sized breaker fuse or not time delayed Short in system Getting water in enclosure Drain plugged Drain tube kinked Enclosure not sealed allowing humidity in Mounting gasket damaged For additional technical information i e amp draw pre...

Страница 11: ...ts will assume the balance of the warranty on the part returned for warranty consideration Please be advised According to the Federal Register no person maintaining servicing repairing or disposing of appliances may knowingly vent or otherwise release into the environment any class I or class II substance used as refrigerant McLean Thermal assumes no liability beyond the repair or replacement of i...

Отзывы: