1 / 2
E507S-2LS-2
DOUBLE-POLE LINE-SENSING THERMOSTAT FOR HAZARDOUS LOCATIONS
INSTALLATION INSTRUCTIONS
THERMAL MANAGEMENT SOLUTIONS
EN-DigiTraceE507S2LS2-IM-H56914 01/13
DESCRIPTION
The E507S-2LS-2 thermostat is designed for controlling heat-
tracing systems in hazardous locations. The thermostat functions
as a DPST switch. The DPST switch will enable and disable current
flow in both buses of the heat-tracing cable.
The E507S-2LS-2 can be used to control heat-tracing circuits in a
pipe-sensing mode (see Figure 1 on back page).
Note: Do not use this thermostat to control two separate heat-
tracing circuits.
ADDITIONAL MATERIAL REQUIRED
ǩ
AT-180 aluminum tape
APPROVALS
SPECIFICATIONS
Enclosure
NEMA 4, 7, 9, lacquer-coated cast-aluminum
housing, stainless-steel hardware
Entries
One 3/4 in. NPT conduit hub
Set point range
25°F to 325°F (–4°C to 163°C)
Sensor exposure
limits
–40°F to 420°F (–40°C to 215°C)
Housing exposure
limits
–40°F to 140°F (–40°C to 60°C)
Switch
DPST
Electrical rating
22 A at 208/240 Vac
Relay coil
208–240 Vac, 4 VA
Accuracy
±6°F (±3.3°C)
Deadband
2°F to 12°F (1.1°C to 6.7°C) above actuation
temperature
Set point
repeatability
±3°F (±1.7°C)
Sensor type
Fluid-filled (silicone) bulb and 9 ft (2.7 m)
capillary
Sensor material
300 series stainless steel
Connection
terminals
Screw terminals, 10–14 AWG (2–5 mm
2
)
Class I, Div. 1 and 2, Groups B, C, D
Class II, Div. 1 and 2, Groups E, F, G
Class III
Hazardous locations
This component is an electrical device. It must be installed
correctly to ensure proper operation and to prevent shock or
fire. Read these important warnings and carefully follow all the
installation instructions.
Component approvals and performance are based on the use of
specified parts only. Do not use substitute parts or vinyl electrical
tape to make connections.
WARNING:
4.0 in (102 mm)
8.0 in
approx.
4.5 in (114 mm)
Ø.28 in (7 mm)
mounting hole
(4X)
4.5 in
(114 mm)
6.6 in
(168 mm)
4.0 in
(102 mm)
Adjusting
knob
Removable
knob cover
1.2 in
(30 mm)
3⁄4 in NPT conduit entry
2.0 in
(50 mm)
6.0 in (153 mm)
Terminal
block