Pentair Digitrace E507S-2LS-2 Скачать руководство пользователя страница 1

1 / 2

E507S-2LS-2

DOUBLE-POLE LINE-SENSING THERMOSTAT FOR HAZARDOUS LOCATIONS  

INSTALLATION INSTRUCTIONS

THERMAL MANAGEMENT SOLUTIONS

EN-DigiTraceE507S2LS2-IM-H56914      01/13

DESCRIPTION

The E507S-2LS-2 thermostat is designed for controlling heat-
tracing systems in hazardous locations. The thermostat functions 
as a DPST switch. The DPST switch will enable and  disable current 
flow in both buses of the  heat-tracing cable.

The E507S-2LS-2 can be used to control heat-tracing circuits in a 
pipe-sensing mode (see Figure 1 on back page).

Note: Do not use this thermostat to control two separate heat-
tracing circuits.

ADDITIONAL MATERIAL REQUIRED

ǩ

AT-180 aluminum tape

APPROVALS

SPECIFICATIONS

Enclosure

NEMA 4, 7, 9, lacquer-coated cast-aluminum 
housing, stainless-steel hardware

Entries

One 3/4 in. NPT conduit hub

Set point range

25°F to 325°F (–4°C to 163°C)

Sensor exposure 
limits

–40°F to 420°F (–40°C to 215°C)

Housing exposure 
limits

–40°F to 140°F (–40°C to 60°C)

Switch

DPST

Electrical rating

22 A at 208/240 Vac

Relay coil

208–240 Vac, 4 VA

Accuracy

±6°F (±3.3°C)

Deadband

2°F to 12°F (1.1°C to 6.7°C) above actuation 
temperature

Set point  
repeatability

±3°F (±1.7°C) 

Sensor type

Fluid-filled (silicone) bulb and 9 ft (2.7 m) 
capillary

Sensor material

300 series stainless steel

Connection  
terminals

Screw terminals, 10–14 AWG (2–5 mm

2

)

Class I, Div. 1 and 2, Groups B, C, D
Class II, Div. 1 and 2, Groups E, F, G
Class III

Hazardous locations

This component is an electrical device. It must be installed 
correctly to ensure proper operation and to prevent shock or 
fire. Read these important warnings and carefully follow all the 
installation instructions.

Component approvals and performance are based on the use of 
specified parts only. Do not use substitute parts or vinyl electrical 
tape to make connections.

WARNING:

4.0 in (102 mm)

8.0 in

approx.

4.5 in (114 mm)

Ø.28 in (7 mm) 
mounting hole 
(4X)

4.5 in

(114 mm)

6.6 in

(168 mm)

4.0 in

(102 mm)

Adjusting
knob

Removable
knob cover

1.2 in
(30 mm)

3⁄4 in NPT conduit entry

2.0 in

(50 mm)

6.0 in (153 mm)

Terminal

block