background image

 

 

Installation Instructions  P70 

 

Issue Date  0918 

 

©  2018 Johnson Controls

 

1

 

  Part No. 24-7664-1938, Rev. F 

 

P70, P72, and P170 Series Controls for 

High Pressure Applications

 

Application 

P70, P72, and P170 Series Controls for High Pressure 
Applications provide high-side pressure control on 
commercial refrigeration and air conditioning 
applications. 

IMPORTANT: 

Except for those models listed 

as 

Refrigeration Pressure Limiting Controls

, use the 

P70, P72, and P170 Series Controls for High 
Pressure Applications only as an operating control. 
Where failure or malfunction of a P70, P72, or P170 
pressure control could lead to personal injury or 
property damage to the controlled equipment or 
other property, additional precautions must be 
designed into the control system. Incorporate and 
maintain other devices such as supervisory or alarm 
systems or safety or limit controls intended to warn 
of, or protect against, failure or malfunction of the 
P70, P72, or P170 pressure control. 

 

 

P70C, P70D, P170C, and P170D type models

 

with Single-Pole Single-Throw (SPST) Open-High 
switch action are the most popular models and are 
typically used as high pressure Cutout controls. 
The 

C type models

 are automatic reset controls. 

The 

D type models

 have a manual reset lockout 

mechanism. Some 

P70C, P70D, P170C, and 

P170D type models

 are UL Listed as refrigeration 

pressure limiting controls. See Table 2 for 
standard models available. 

 

P70A and P170A type models

 feature SPST 

Open-Low switch action and typically are used for 
condenser-fan cycling control. 

 

P70 and P170 Series models

 with Single-Pole 

Double-Throw (SPDT), or 4-Wire, 2-Circuit switch 
action allow users to install alarm devices or other 
control circuits. 

 

P72 Series models 

have a Double-Pole 

Single-Throw (DPST) switch with load-carrying 
contacts that can provide direct control of 208-240 
VAC single-phase motors up to 3 hp, 480 and 600 
VAC single-phase noncompressor motors, and 
208-220 VAC 3-phase motors up to 5 hp. See 
Table 6. 

Controls are available in several pressure ranges and 
are compatible with most common refrigerants. 

 

They may also be used on air, water and other 
noncorrosive fluid applications. Ammonia compatible 
models are also available. 

!

  CAUTION:  Risk of Property Damage. 

Mount the pressure control separately from the 
electrical cabinet and seal all electrical piping to 
prevent ammonia from migrating to electrical 
components. Where there may be exposure to 
ammonia, use only ammonia compatible control 
modules and pressure connections. System 
shutdown due to improper adjustment may cause 
property damage. 

 

The 

Manual Reset Lockout

 mechanism does not 

allow the pressure control to automatically reset after 
the control has Cutout, providing shutdown capability 
for unmonitored equipment. See 

Manual Reset 

Operation. 

NEMA 1 enclosures

 are standard on most models. 

NEMA 3R enclosures

 are also available on quanity 

orders. 

Dimensions 

Mounting Hole

3/16

5

Diameter

2-Mounting Holes

10-32 UNF-2B 

Thread

4

101

3-1/16

77

1-5/16

34

1/16

2

15/16

24

2-1/16

53

1-1/4

33

3/16

4

3/16

4

7/8

22 Conduit Hole

5/16

8

3-1/4

83

5/16

8

1

25

1-1/8

29

1-7/8

49

5/16

8

3/8

10

X

3/16

5

Diameter

Mounting Hole

(NEMA 1/2 in.)

3-1/4 

83

2-13/16

71

1-11/16

43

15/16

(24)

15/16

(24)

 

Figure 1: Dimensions for P70, P72, and P170 

Pressure Controls with NEMA 1 Enclosures, 

in. (mm) 

Содержание P170A

Страница 1: ...models with Single Pole Double Throw SPDT or 4 Wire 2 Circuit switch action allow users to install alarm devices or other control circuits P72 Series models have a Double Pole Single Throw DPST switch...

Страница 2: ...mounting screws supplied with the Universal Mounting Bracket to avoid damaging internal components Be careful not to distort or bend the control case when mounting the control to an uneven surface Us...

Страница 3: ...n wiring the control WARNING Risk of Electrical Shock Disconnect each of multiple power supplies before making electrical connections More than one disconnect may be required to completely de energize...

Страница 4: ...ut Automatic Reset High pressure Cutout controls with automatic reset have a scaleplate that displays the Cut In and Cutout setpoints See the visible scale on the control Turn the range screw to adjus...

Страница 5: ...operation Manual Reset Operation Pressure controls with the Manual Reset option lock out when they reach Cutout pressure and must be manually reset by the user to restart the controlled equipment The...

Страница 6: ...or All Range Control Models for Noncorrosive Refrigerants P70CA 2 SPST Open High 50 to 500 345 to 3448 Minimum 60 414 Maximum 150 1034 1 4 in Male Flare Connector 525 3620 P70CA 3 36 in Capillary with...

Страница 7: ...or models not included in this table contact the Refrigeration Application Engineering Group at 1 800 275 5676 for details and availability Note See Dimensions and Technical Specifications for additio...

Страница 8: ...e Amperes 16 0 9 2 8 0 7 2 6 0 6 0 6 0 6 0 Pilot Duty for both sets of contacts 125 VA at 24 to 600 VAC 57 5 VA at 120 to 300 VDC Not for compressor motor loads Table 6 DPST Electrical Ratings P72A B...

Страница 9: ...ntrols 60 lb 27 2 kg Compliance For information on specific models contact the Refrigeration Application Engineering Group at 1 800 275 5676 Accessories 271 51 Universal Mounting Bracket supplied with...