Penn A421ABC-02C Скачать руководство пользователя страница 9

A421 Series Standard Electronic Temperature Controls Installation Instructions

9

A421 Control Parameter Setup Menus

The A421 temperature controls provide a Basic and an 
Advanced setup menu that allow you to scroll through 
the parameter setup codes, view and edit parameter 
values, and set up your control for your application 
requirement. The control also has a Restricted 
(adjustment) menu. See 

Restricting User Adjustment

 

for more information.

Note:

The A421 control retains a copy of the saved 

parameter values in memory. When you change and 
save a new value, the new value immediately 
overwrites the previous value and is saved to memory. 
In the event of a power failure, brown out, or when you 
disconnect power from the control, all of the current 
parameter values in memory are retained. 
Reconnecting power to the control restores all of the 
saved values.

Menu Navigation Guidelines

The A421 control buttons and display operate the 
same in Basic and Advanced menu options. While in 
any parameter 

code

 screen, the following behavior is 

observed:

The parameter code flashes on and off.

Press 

 or 

 to navigate through all of the 

parameter code screens.

To exit either menu and return to the Main screen, 
press 

 and 

 simultaneously.

While in any parameter 

value

 screen, the following 

behavior is observed: 

The parameter value flashes on and off.

Press 

 or 

 to scroll through all of the available 

parameter values for the associated parameter 
code.

With the preferred parameter value displayed, 
press 

MENU

 to save the value and go to the next 

parameter code screen.

Note:

If you do not press

 MENU

 to save a new value, 

the control reverts to the last saved value.

After 30 seconds of inactivity, while in any screen, the 
control reverts to the Main screen.

Basic Menu

The Basic menu allows you to quickly edit the 

On

 and 

OFF

 temperature values, as well as the Sensor Failure 

Mode (

SF

) and Anti-Short Cycle Delay (

ASd

) value.

See 

Parameter Codes and Modes of Operation

 and 

Table 4 for more information regarding parameter 
codes, usable parameter values, and default values.

On

Relay On Temperature (Basic and Advanced)

-40 to 212 ºF (-40 to 100 ºC) 

30 ºF

ASd

Anti-Short Cycle Delay (Basic and Advanced)

0 to 12 (minutes)

0 (minute)

tSb

Temperature Setback (Advanced only)

-50 to 50 ºF (-30 to 30 ºC)

0 (ºF)

So

Sensor Offset Adjustment (Advanced only)

-5 to 5 ºF (-3 to 3 ºC)

0 (ºF)

HtS

High Temperature Stop (Advanced only)

-40 to 212 ºF (-40 to 100 ºC) 

212 ºF 

LtS

Low Temperature Stop (Advanced only)

-40 to 212 ºF (-40 to 100 ºC) 

-40 ºF 

SF

Sensor Failure Action (Basic and Advanced)

0 = output relay de-energized
1 = output relay energized

1 (output relay energized)

bLL

LCD Backlight Brightness Level Adjustment 
(Advanced only)

0 to 10; 0 = backlight off, 
10 = brightest backlight setting

10 (brightest backlight)

Table 4:  Standard Parameter Setup Codes, Descriptions, Range of Values, and Default Values
  (Part 2 of 2)

Parameter 
Code

Parameter Description (Menu)

Range of Usable Values

Factory Default 
Values Shown

Содержание A421ABC-02C

Страница 1: ...A421 control could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain ot...

Страница 2: ...is connected to a standard A421 control the range of usable values is restricted by the control to 40 to 212 F 40 to 100 C See Wiring Technical Specifications and refer to the A99B Series Temperature...

Страница 3: ...rness between the enclosure base and cover more than 180 Wiring WARNING Risk of Electric Shock Disconnect or isolate all power supplies before making electrical connections More than one disconnection...

Страница 4: ...l does not provide any internal power to the TB2 terminals or relay contacts The A421 control simply energizes and de energizes the relay to open and close the contacts based on the On OFF temperature...

Страница 5: ...d Wire Sizes TB1 24 VAC Models LN Low Voltage 24 VAC Control Power Common Connect the 24 VAC supply power to operate the control 28 AWG to 12 AWG 0 08 mm2 to 4 0 mm2 24V Low Voltage 24 VAC Control Pow...

Страница 6: ...12 AWG 0 08 mm2 to 4 0 mm2 LNO Line Voltage SPDT Relay Normally Open Contact Connects controlled equipment to the Line Voltage Normally Open LNO contact on the SPDT relay When LC is closed to LNO the...

Страница 7: ...and the green LED goes off The range of usable temperature values is 40 to 212 F 40 to 100 C in 1 increments Relay On Temperature On Select the temperature at which the output relay energizes the LC t...

Страница 8: ...ode the effective On and OFF setback values On tBs and OFF tBs can be greater than the selected HtS value or less than the selected LtS value Temperature Setback tSb Select a temperature value for set...

Страница 9: ...gh all of the available parameter values for the associated parameter code With the preferred parameter value displayed press MENU to save the value and go to the next parameter code screen Note If yo...

Страница 10: ...Modes of Operation and Table 4 for more information regarding parameter codes usable parameter values and default values 1 With the Main screen displayed press MENU The LCD displays OFF which is the f...

Страница 11: ...On value automatically shifts equal to the OFF value adjustment The OFF value can only be adjusted to values that maintain the entire control band within the restricted temperature adjustment range de...

Страница 12: ...OFF value and return to the OFF code screen 5 Press and simultaneously to return to the Main screen Troubleshooting Fault Codes A421 Series controls display fault codes on the LCD as described in Tabl...

Страница 13: ...ad from the output relay terminals b Ensure that the Parameter Adjustments jumper is installed so that access to adjust parameters is unrestricted c Reconnect the sensor leads and supply power to the...

Страница 14: ...l Type 4X NEMA IP66 watertight enclosure for surface mount applications Rated for 120 240 VAC Includes an A99BB 200C temperature sensor with 6 6 ft 2 0 m cable A421GBF 02C Low Voltage Type 1 Electroni...

Страница 15: ...erating temperature range 40 to 248 F 40 to 120 C A99CB 200C PTC Temperature Sensor Extended probe 6 in 15 2 cm with 6 6 ft 2 0 m PVC cable Ambient operating temperature range 40 to 212 F 40 to 100 C...

Страница 16: ...lass B limits Europe CE Mark Johnson Controls Inc declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive Low Voltage Directive A...

Страница 17: ...rd A421 control model the range of displayed temperature values is 40 to 212 F or 40 to 100 C The performance specifications are nominal and conform to acceptable industry standards For application at...

Отзывы: