Rev. 1.0
Penguin Computing
23
Removing the System from the Rack
To remove a unit from the rack:
Step 1.
Turn off the system and disconnect it from peripherals and from the electrical outlet. While
your installation partner is supporting the system’s weight:
Step 2.
Loosen the screws attaching the brackets to the rack. Do not remove them yet.
Step 3.
Loosen the screws attaching the blades to the rack, and pull the blades towards you, while
your partner is holding the system.
Step 4.
Extract the loosened screws from Step 2 and dismount the system from the rack.
Step 5.
Remove the rails and brackets from the chassis by unscrewing 8 screws.
Telescopic Rail Kit for Arctica 3200cs
There are two installation kit options:
•
Standard depth systems should be mounted using the standard rail kit.
•
Short depth systems can be mounted using either of the rail kits.
Table 5: Installation Kit
Penguin PN
Rack Size and Rack Depth Range
10027052
Short (17"-24" \ 43.1 to 61 cm)
10027053
Standard (24"-34" \ 61 to 86.3 cm)
The following parts are included in the rail kit package (see Figure 14: Rack Rail Kit Parts):
•
1x Right inner rail (A)
•
1x Left inner rail (B)
•
2x Outer rails (C)
•
2x Outer rails (D)
•
10x M6 Standard cage nuts¹ ² and 10x M6 Standard pan-head Phillips screws¹ (E)