DIAGNOSTIC
In case of anomalies, the
VISION100 THR
controller warns the operator using alarm codes
shown by the display and an acoustic signal emitted by a buzzer inside the Operational console. In
case an alarm condition occurs, the display will show one of the following messages:
ALARM CODE
POSSIBLE CAUSE
OPERATION TO BE CARRIED OUT
E0
Functional anomaly of the ambient probe
Check ambient probe state.
If problem persists, replace the
probe.
E1
Functional anomaly of the humidity probe
Check state and connection of
humidity probe.
If problem persists, replace the
probe.
E2
Functional anomaly of the defrosting probe
(In this case, any defrosting will have d5 duration)
Check defrosting probe state.
If problem persists, replace the
probe.
E3
Eeprom alarm
An error has been detected in the EEPROM
memory. (All outputs are deactivated except the
alarm outputs)
Switch the equipment off and on
again.
E4
Software compatibility error
Check correct combination
between MASTER board and
Console board.
E6
Discharged battery alarm
Replace the Console lithium
battery (CR2032 type).
Ec
Main alarm
(e.g. Thermal protection or max.
pressure switch)
(All outputs are deactivated except the alarm output.
if present)
Check compressor absorption.
If problem persists, contact the
after-sales technical assistance
service.
En
No connection between Console and MASTER
board
.
Check connection between the
two units.
If problem persists, contact the
after-sales technical assistance
service.
Eu
Minimum or maximum humidity alarm.
A humidity higher or lower to that set for minimum or
maximum humidity alarm has been reached in the
ambient (
See variables AU1 and AU2, user
programming level
)
Check humidity management.
The probe does not correctly
detect the humidity.
Et
+
Temperature
on display is
flashing
Minimum or maximum temperature alarm.
A temperature higher or lower to that set for
minimum or maximum temperature alarm has been
reached in the ambient (
See variables At1 and At2,
user programming level
)
Check the compressor state.
The probe incorrectly detects the
temperature or the stop/start
control of the compressor does
not work.
Ed
Limit Timeout for dehumidification
Check humidity management.
The probe does not correctly
detect the humidity.
CHAPTER 7: DIAGNOSTIC
CHAP. 7 - Diagnostic