VISION
100
THR
Page 19
USE AND MAINTENANCE MANUAL
Rev. 02-18
btF
Differential
of temperature referred to
Setpoint for
COLD LOCK
.
It constitutes the SET-btF limit below which
the cold call relay (3-4) and the
Dehumidification relay (25-26) are
disabled.
0 ÷ 20 °C
0 = Disabled
0
btC
Differential
of temperature referred to
Setpoint for
HOT LOCK
.
It constitutes the SET+btC limit above
which the hot call relay (5-6), the
Humidification relay (11-12) and the
Dehumidification relay (25-26) are
disabled.
0 ÷ 20 °C
0 = Disabled
0
dEt
Limit time for DEHUMIDIFICATION
.
If the dehumidification request is not
satisfied (reaching of humidity SET) within
the time (dEt), the variable (dEO) is taken
into consideration for the operation to be
performed. Counting starts at every new
dehumidification request.
(0 min ÷ 4 hours)
(1 min steps)
0 = Disabled
0
dEo
Operation to be performed in case limit
Timeout for dehumidification (dEt)
intervenes
dEO = 0 an alarm signal (Ed) +
alarm relay is given. The alarm is
displayed even when humidity set is
achieved; it does not lock the normal
functioning and once silenced, the dEt
count re-starts.
dEO = 1 a refreshment of the duration (dr)
is launched and the timer relating to the
interval (Pr), if present, is recharged.
0 = alarm only
1 = a refreshment is
performed.
0
Ad
Net address for connection to supervision
system TELENET.
0 ÷ 31
0
Aut
Automatic cycles management or via
TeleNET. For managing the cycles via
TeleNET to set Aut=1
0 = local cycles
1 =
TeleNET management
0
Cg
Seasoning or germination selection
0 = seasoning cycles active
1 = germination day/night
cycle active
0
CgA
Not used.
0
0
tg2
Not used.
0
0
CHAP. 5 - Data programming