PLUS 100 AB

 

 

 

 
 
 
 
 
 
 
 
 
 
 

rev 01-08 

Содержание PLUS 100 AB

Страница 1: ...PLUS 100 AB rev 01 08...

Страница 2: ...PLUS 100 AB Page 2 Rev 01 08 MANUALE D USO E MANUTENZIONE...

Страница 3: ...ures Page 13 5 5 Key to symbols Page 13 5 6 Setting and displaying the set points Page 14 5 7 Programming the type of work Page 18 5 8 Level 1 programming Page 19 5 9 List of Level 1 variables Page 20...

Страница 4: ...nents on a refrigeration unit The board allows the user to control and power the main refrigeration system components such as the compressor evaporator fans defrosting elements and room light There is...

Страница 5: ...IONS IDENTIFICATION DATA The unit described in this manual has on its side an ID plate showing all the relevant identification data Name of Manufacturer Code and model of electrical board Serial numbe...

Страница 6: ...ts 4 Minimise the length of connector wires so that wiring does not twist into a spiral shape as this could have negative effects on the electronics 5 Fit a general protection fuse upstream from the e...

Страница 7: ...evaporator temperature System control activation deactivation System warnings sensor error min max temperature alarms compressor safety device Evaporator fan control Automatic manual defrost control...

Страница 8: ...5 C Read range 45 45 PLUS100 AB Output characteristics max applicable load 230 V AC Compressor non powered contact 1500 W AC3 Elements non powered contact 1500 W AC1 Fans non powered contact 500 W AC...

Страница 9: ...modifications made to wiring and or internal components or any tasks carried out in a way that fails to comply with the information instructions in this manual shall not only render the warranty null...

Страница 10: ...onths also remain lit 2 Indicator warning LEDs a Cold cooling in progress b Quick freezing rapid freezing in progress c Temperature freezing cooling freezing by temperature PR1 PR2 PR3 d Time freezing...

Страница 11: ...ew seconds the cooling cycle starts 2 UP MUTE BUZZER ALARM key if pressed for 5 seconds together with key 1 recorded alarms are displayed 3 STAND BY key system shuts down room temperature light flashe...

Страница 12: ...h see setting on parameter tEu on 1st level programming parameters during programming for values greater than 45 C the word HOT is displayed 3 Time date time parameter values 4 Programming control is...

Страница 13: ...ogramming directly from Level 1 you must exit the programming mode first KEY TO SYMBOLS For purposes of practicality the following symbols are used t the UP key is used to increase values and mute the...

Страница 14: ...rature based cooling Program for product cooling by positive temperature Cooling ends when the core of the product reaches temperature At1 A maximum safety time is set on parameter Ab1 When cooling is...

Страница 15: ...nues until the end of the cycle even in the event of a power cut or a rise in temperature Freezing ends when the product core reaches temperature At3 A maximum safety time is set on Ab3 At the end of...

Страница 16: ...tically goes to storage mode with the ST5 setting The compressor works continuously VARIABLES MEANING VALUES DEFAULT At3 End of PR3 Cooling Freezing temperature 45 45 C 20 C ST3 Storage temperature at...

Страница 17: ...ssor during cooling the compressor stops if ambient temperature reaches ST6 r1 The compressor is reactivated on reaching ST6 During freezing the compressor works continuously VARIABLES MEANING VALUES...

Страница 18: ...the t and u keys 3 Select the variable to be modified using the t or u key 4 When the variable has been selected it is possible to display the setting by pressing SET to modify the setting by pressin...

Страница 19: ...e defrost LED on the front of the panel flashes 0 30 min 0 min F5 Fan pause after defrost minutes Allows fans to be kept at standstill for a time F5 after dripping This time is counted from the end of...

Страница 20: ...u key 4 When configuration settings have been completed you can exit the menu by pressing the t and u keys simultaneously and keeping them pressed until the room temperature value reappears 5 Changes...

Страница 21: ...closes the remote defrost contact trips or when time d3 expires 0 evaporator sensor present 1 evaporator sensor absent 0 dE1 Product sensor presence With dE1 1 it is possible to disconnect the product...

Страница 22: ...porator sensor is higher than this value 45 45 C 45 C tA NO NC alarm relay switching activates when alarm is on 1 deactivates when alarm is on 1 rA Control relay door anti fogging element 0 alarm rela...

Страница 23: ...R6 using the up down keys Start the selected program by pressing key 1 for a few seconds It is also possible to start a program starting from stand by mode To confirm the start of a cycle the warning...

Страница 24: ...e defrost cycle in inversion mode The compressor relay and defrost relay are activated throughout the defrost phase To ensure proper control of the system the installer must use the defrost output thi...

Страница 25: ...ing data correctly Contact technical assistance service E6 Flat battery alarm the controller will function for at least another 20 days subsequently any power loss to the board will involve loss of ti...

Страница 26: ...inside the cold room has exceeded the min or max temperature alarm setting see variables A1 and A2 user programming level Check that the compressor is working properly Sensor not reading temperature p...

Страница 27: ...lectrical equipment employed within certain voltage limits and subsequent amendments 89 336 CEE Direttiva del Consiglio per l unificazione delle normative dei Paesi CEE relativa alla compatibilit elet...

Страница 28: ...ck out 9 15 Fan overload 9 16 Remote defrost end 9 17 Door switch 9 18 Compressor safety device Outputs section no voltage contacts 31 32 Freezing solenoid 33 34 Cooling solenoid 35 36 Alarm 37 38 Roo...

Страница 29: ...PLUS 100 AB Page 29 Rev 01 08 MANUALE D USO E MANUTENZIONE Notes...

Страница 30: ...PLUS 100 AB Page 30 MANUALE D USO E MANUTENZIONE Rev 01 04...

Страница 31: ...PLUS 100 AB Page 31 Rev 01 08 MANUALE D USO E MANUTENZIONE...