DIN NANO FSC
Chapter 5
– Data Programming
USER AND MAINTENANCE MANUAL
Rev. 03-18
Page 16
nSC
Correction for the compressor SET
during night operation (energy
saving)
During night operation the
Compressor set is:
Compressor Set = Set + NSC
-
5,0 … 5,0 Bar
0,0 Bar
-
20,0 … 20,0 °C
0,0 °C
Ad
Network address for connection to the
TeleNET or Modbus supervision
system
0 ÷ 31 (with SEr=0)
1 ÷ 247 (with SEr=1)
1
Ser
RS-485 communication protocol
0 = TeleNET protocol
1 = Modbus-RTU protocol
0
Bdr
Modbus baudrate.
0 = 300 baud
1 = 600 baud
2 = 1200 baud
3 = 2400 baud
4 = 4800 baud
5 = 9600 baud
6 = 14400 baud
7 = 19200 baud
8 = 38400 baud
5
Prt
Modbus parity checking.
0 = no parity bit
1 = even parity bit
2 = odd parity bit
0
P1
Password: type of protection
(Active when PA is not 0)
0 = shows only the set point and permits
deactivation of the alarms.
1 = disables access to level 1, 2 and 3
programming (access permitted to all other
functions).
2 = disables access to level 2 and 3
programming (access permitted to all other
functions).
3 = disables access to level 3 programming
(access permitted to all other functions).
3
PA
Password
(see P1 for the type of protection)
0...999
0 =
function disabled
0
Yr
Set year
0 … 99
14
Mo
Set month
1 … 12
1
dy
Set day
1 … 31
1
Hr
Set hour
0 … 23
12
min
Set minutes
0 … 59
30
dEF
Reserved parameter
read-only
reL
Software release
read-only