![Peco TA170 Скачать руководство пользователя страница 1](http://html1.mh-extra.com/html/peco/ta170/ta170_manual_1519917001.webp)
TA/TB170 THERMOSTAT
READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
THERMOSTAT.
Failure to observe safety information and comply with instruc-
tions could result in PERSONAL INJURY, DEATH AND/OR
PROPERTY DAMAGE.
To avoid electrical shock or damage to equipment, disconnect
power before installing or servicing and use only wiring with
insulation rated for full thermostat operating voltage.
Before installing this control, the Voltage Selection Switch must
be placed in the correct position. See instructions.
To avoid potential fire and/or explosion do not use in potentially
flammable or explosive atmospheres.
Retain these instructions for future reference. This product,
when installed, will be part of an engineered system whose
specifications and performance characteristics are not designed
or controlled by PECO. You must review your application and
national and local codes to assure that your installation will be
functional and safe.
•
•
•
•
•
•
WARNING
CAUTION
Use copper wire only, insulate or wire nut all unused leads.
Care should be used to avoid electrostatic discharge to the T170
thermostat.
This unit has configuration jumpers. You may need to reconfigure
this thermostat for your application.
applications and features
For 2 or 4 Pipe Fan Coil and On/Off Control Applications
System Selection: Off-Heat-Cool-Auto-Setback
6 Outputs: 1H, 1C, Up to 3 Fan, OA Damper
Fan Control: 1-3 Speeds
Cycling (Auto) or Continuous (On)
Automatic Fan Speed Staging
(TB170 models only)
Connections for:
Fan Coil Pipe Sensor
Remote Temperature Probe
Occupancy Control
Door Switch or Setback
Condensate Overflow
specifications
Temperature Set Point Range
50 to 90°F / 10 to 32°C
Differential
1°
Memory – Back-Up
EEPROM, No batteries required,
Stores settings for unlimited
time.
Mounting
Installs on standard 4” x 4”
device box with a 2” x 4”
horizontal mud ring
•
•
•
•
•
•
•
•
•
•
•
▲
!
Physical Dimensions
4.4”H x 5.8”W x 1.1”D
Agency Approvals
UL, UL Canada
Electrical Ratings
(see table below)
Switching
Inductive
Voltage
Rating
FLA
LRA
Resistive
Amps
Pilot
Duty
24 VAC
NA
NA
NA
24 VA
120 VAC
5.8
34.8
6.0
125 VA
240 VAC
2.9
17.4
5.0
125 VA
277 VAC
2.4
14.4
4.2
125 VA
COMBINED LOAD CURRENT NOT TO EXCEED 20 AMPS
MOUNT ONLY TO A GROUNDED METALLIC BOX
LOW VOLTAGE WIRING IS CLASS 2
installation
New Installations
The thermostat should be used indoors only. It should be mounted on
an inner wall in a location with freely circulating air, and where it will be
responsive to changes in room temperature. Avoid mounting near heat
generating appliances (i.e. TV, heater, refrigerator), or in direct sunlight.
Remove Old Thermostat
Turn off power to thermostat at main fuse or circuit breaker box.
Ensure that ALL power is disconnected.
to prevent electri-
cal shock and /or equipment damage, disconnect electrical
power to the system at the main fuse or circuit breaker until
installation is complete.
Remove the front cover of old thermostat. With wires still at
-
tached, remove wall plate from the wall. If the old thermostat has
a wall mounting plate, remove the thermostat and the wall mount-
ing plate as an assembly.
Before removing wires from old thermostat, label each wire
with the terminal designation from which it was attached.
Disconnect the wires from the old thermostat one at a time.
do
not let wires fall back into the wall.
Jumper and Circuit Board Selections
Voltage selection switch
: This switch must be placed in the appropri-
ate position prior to application of power.
24V
= 24 VAC
110-277 V = 120, 240 or 277 VAC
Jp1 Jumper selection – remote temperature sensor
:
Local Sensing – Install JP1
Remote Sensing – Remove JP1 – Accessory sensors are avail-
able in standard 60” lengths but can be extended to meet applica
-
tion requirements.
1.
2.
3.
4.
•
•
•
•
© COPYRIGHT 2007 PECO, INC. ALL RIGHTS RESERVED.
P/N 69287 3220-2084 REV 0 PAGE 1
▲
!
▲
!
AUTO
COOL
AUTO LOMEDHI OFF
FAN ON
HEAT
SYSTEM
FAN
SPEED
HOLD F/C
▲
!