PowerWave 2 Bus System BCMS Setup and Operation
Cntl Nr: PM375107-002
24
3.8.1
Set Unit Name
Enter the device name in
Unit Name
, up to (16) characters, then click
Set
.
Unit Name
is a contiguous
group of (8) 2-byte Modbus registers in the points list (Figure 14). It is easier to enter the name here than
to set individual register values.
Figure 14 Setup Data Tab: Enter Device or Unit Name
3.8.2
Setting Point Values and Clearing Alarms
You can set point values or clear alarms from the Data Tab screen (Figure 15).
Figure 15 Setup Data Tab: Selecting and Changing Specific Point Values
1.
Use drop-down box to
select device
. The first device is usually the
INP PM
(Input
Power Monitor for monitoring source power in the end feed).
The remaining devices are Tap Off Boxes, identified as
IBUS
, the associated monitoring PCB.
3. Set
: Input the data value for the
selected Modbus register; click
Set
to
write the data to the Modbus register.
4. Clear
: If the selected Modbus register is an alarm
register, click
Clear
to clear alarms. (You cannot set
alarm values.)
2.
Scroll through points and click on point
to
select point
. The point number, name,
and Modbus register data appear in the
Write to Modbus