PowerWave 2 Bus System BCMS Setup and Operation
Cntl Nr: PM375107-002
16
o
Set Modbus register values
o
Clear individual alarm registers
•
Window tab
—
for use by PDI engineering and service; not for customer use.
Figure 8 Accumulator Setup: Setup Tab
3.4
Setup Tab
The Setup Tab (Figure 8) lets you identify the monitored devices along the bus run, which are source
input power or Tap Off Boxes. Because devices are on a bus, devices are not identified by their order on
the bus.
1.
Devices are listed by the PCBs that monitor power:
a)
Input Power Source:
INP PM = Input Power Monitor PCB. This PCB monitors the input power
source. There is only be one of these PCBs.
b)
Tap Off Box:
IBUS = iBus PCB. This PCB is in the Tap Off Box and monitors up to (6) poles.
c)
The Number of Devices = INP PM + IBUS counts, or
= (0) input power source and
≤
(32) Tap Off Boxes, or
= (1) input power source and
≤
(31) Tap Off Boxes.
d)
Note:
If the bus run is monitored from the 7" Local Display, you are limited to (1) power feed and
up to (15) Tap Off Boxes in the bus run. The number of Tap Off Boxes is not increased if you do
not monitor the input power source.
Setup Tab
lists all
devices
that the
Accumulator has found on the bus run.
A “device” is a logic unit associated with
a Points List. There are two device types:
INP PM
(Input Power Monitor PCB):
monitors input power source at power
feed
IBUS
(iBus PCB) in Tap Off Box:
monitors up to (6) poles in a Tap Off Box
(4) Setup tabs