1.3
Safety category ratings
Category rating
Brief description
Typical applications
Cat II
Single phase receptacles
and connected loads
• Household appliances,
power tools
• Outlets more than 30 ft
(10 m) from a Cat III source
• Outlets more than 60 ft
(20 m) from a Cat IV source
Cat III
Three phase circuits and
single phase lighting circuits
in commercial buildings
• Equipment in fixed
installations such as
3-phase motors, switchgear
and distribution panels
• Lighting circuits in
commercial buildings
• Feeder lines in industrial
plants
• Any device or branch circuit
that is close to a Cat III
source
The measurement category (CAT) rating and voltage rating is determined by a combination of the
meter, test probes and any accessories connected to the meter and test probes. The combination
rating is the LOWEST of any individual component.
WARNING
: Operation is limited to CAT II applications when the insulated tips are removed from
one or both test probes. Refer to the input limits section in this manual for maximum voltage
ratings.
1 – Insulated tip on
2 – Insulated tip removed