Installation Instructions

PA3A, PA4A

R--410A SPLIT--SYSTEM

AIR CONDITIONER

1--1/2 -- 5 TONS (018--060)

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other

conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your

distributor or branch for information or assistance. The qualified

installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions

packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,

and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions

thoroughly and follow all warnings or cautions included in

literature and attached to the unit. Consult local building codes and
National Electrical Code (NEC) for special requirements.

Recognize safety information. This is the safety--alert symbol

!

!

When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand

these signal words: DANGER, WARNING, and CAUTION. These
words are used with the safety--alert symbol. DANGER identifies

the most serious hazards which

will

result in severe personal injury

or death. WARNING signifies hazards which

could

result in

personal injury or death. CAUTION is used to identify unsafe

practices which

may

result in minor personal injury or product and

property damage. NOTE is used to highlight suggestions which

will

result in enhanced installation, reliability, or operation.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before installing, modifying, or servicing system, main

electrical disconnect switch must be in the OFF position.

There may be more than 1 disconnect switch. Lock out

and tag switch with a suitable warning label.

!

WARNING

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could result in personal injury

or equipment damage.
R--410A refrigerant systems operate at higher pressures than

standard R--22 systems. Do not use R--22 service equipment

or components on R--410A refrigerant equipment.

GENERAL

INSPECT NEW UNIT

After uncrating unit, inspect thoroughly for hidden damage. If

damage is found, notify the transportation company immediately
and file a concealed damage claim.

LOCATION

Check local codes for regulations concerning zoning, noise,
platforms, and other issues.
Locate unit away from fresh air intakes, vents, or bedroom
windows. Noise may carry into the openings and disturb people

inside.
Locate unit in a well drained area, or support unit high enough so

that water runoff will not enter the unit.
Locate unit away from areas where heat, lint, or exhaust fumes will
be discharged onto unit (as from dryer vents).
Locate unit away from recessed or confined areas where
recirculation of discharge air may occur (refer to CLEARANCES

section of this document).
Roof--top installation is acceptable providing the roof will support
the unit and provisions are made for water drainage and

noise/vibration dampening.

NOTE:

Roof mounted units exposed to wind may require wind

baffles. Consult the manufacturer for additional information.

CLEARANCES

When installing, allow sufficient space for airflow clearance,

wiring, refrigerant piping, and service. Allow 30 in. (762 mm)

clearance to service end of unit and 48 in. (1219 mm) above unit.
For proper airflow, a 6 in. (152 mm) clearance on 1 side of unit and

12 in. (305 mm) on all remaining sides must be maintained.
Maintain a distance of 24 in. (610 mm) between units or 18 in.

(457 mm) if no overhang within 12 ft. (7.3 m). Position so water,
snow, or ice from roof or eaves cannot fall directly on unit.
On rooftop applications, locate unit at least 6 in. (152 mm) above

roof surface.
Do not install unit under roof overhangs unless gutters are present.

A minimum vertical clearance of 48 inches (1219 mm) is required
to the overhang.
Inside corner locations on single story structures require

evaluation. Large overhanging soffit may cause air recirculation in
a corner area even though recommended minimum clearances are

maintained. As a guide, locate the unit far enough out so that half
of the discharge grille is out from under the soffit.
When placing two or more units side--by--side, provide a minimum

of 18 inches (457 mm) between units.
Provide minimum service clearance of 24 inches (610 mm) from

control box corner and side service panel.

Содержание PA3A

Страница 1: ...standard R 22 systems Do not use R 22 service equipment or components on R 410A refrigerant equipment GENERAL INSPECT NEW UNIT After uncrating unit inspect thoroughly for hidden damage If damage is fo...

Страница 2: ...tening Unit down If conditions or local codes require the unit be attached in place remove the knockouts in the base pan and install tie down bolts through the holes refer to Fig 1 Contact local distr...

Страница 3: ...ne Application Guide for additional information PERSONAL INJURY and ENVIRONMENTAL HAZARD Failure to relieve system pressure could result in personal injury and or death 1 Relieve pressure and recover...

Страница 4: ...ure to follow this caution may result in product damage Braze with Sil Fos or Phos copper alloy on copper to copper joints and wrap a wet cloth around rear of fitting to prevent damage to TXV CAUTION...

Страница 5: ...cordance with the National Electrical Code and local codes or ordinances Use a copper conductor of the correct size from the grounding lug in control box to a grounded connection in the service panel...

Страница 6: ...m refrigerant to raise the measured temperature Tolerance is 3 F 1 65 C Table 2 R 410A Required Liquid Line Temperature _F MEASURED LIQUID PRESSURE psig RATING PLATE REQUIRED SUBCOOLING TEMPERATURE _F...

Страница 7: ...drainage and clean if necessary Cleanliness These tips will help keep the air conditioner looking better and working more efficiently 1 Free flow of air is essential Keep fences shrubs trash cans and...

Страница 8: ...hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materi...