Configuring the Paxton BLU Expansion Controller

The Paxton BLU Expansion Controller requires configuration and initialization before use. To do this will require a Windows PC or laptop with USB 
ports and internet access, or having the proper installer tool previously installed.

Install the Installer Tool software. This is available to download from the Help page of your installer login to Paxton BLU. You may wish to create a 
desktop shortcut for this application.

Tip: Always ensure you have downloaded the latest version of the Installer tool to ensure you have the most recent version of firmware. The 

latest version is bundled with the Installer Tool application.

Remove the power from the unit.

If your expansion controller is housed in a metal enclosure, you will need to remove the PCB from the plastic mounting bracket in order to attach 
the interface adapter.  Please do so carefully and be sure that the PCB is fully secured to the bracket upon completion of the firmware update 
process.

CAUTION : Make sure the adapter is plugged into both rows of the header on the PCB before you proceed (see image below for 

proper placement and connection)

Power up the controller with the installer tool adapter installed. Note your PC or laptop may need to download a device driver for this 
device so allow this to complete first. Now run the Installer Tool by double clicking the Installer Tool application.

Click on settings and select the COM port that your PC or laptop has assigned to this application. The drop down box lists all available 
COM ports.

Tip: You can confirm the COM port assigned by your computer by navigating to the Windows ‘Device Manager’ and then selecting 
‘Ports (COM & LPT)’
 
Now click on ’View Device Details’ and then on the ‘Get Details’ button. Follow the instruction by power cycling the expansion unit so 
that it goes into its bootloader and provides the required details.

Содержание BLU Expansion Controller

Страница 1: ...Expansion Controller Installation Guide Ins 60006 GD US ...

Страница 2: ...s such debris may create a fire or shock hazard Unpack the unit with care and inspect for transit damage If damage is suspected the unit must not be used or tested but you should immediately contact Paxton technical support to assist in troubleshooting or to provide return authorization INSTALLATION Only qualified and trained personnel familiar with this type of product and who fully understand th...

Страница 3: ...his housing should be fixed to the surface with suitable fasteners screws and wall plugs are provided for this in the fitting kit Also provided are cable ties to secure the cabling and a smaller securing screw for the lid ...

Страница 4: ...maglock wire 12V 24V to the N C terminal instead of N O Repeat the Exit button connections for door 2 if a second door is required Diode Door 1 Reader Keypad Door 2 Reader Keypad To Expansion controller Use shielded data cable Belden 9841 single pair or technical equivalent From Master controller or previous expansion Tamper switch cabinet Expansion controller ...

Страница 5: ... fault reset failed contact Paxton Inc Ok 2 flashes Error 2 Not currently used Ok 3 flashes Error 3 485 IN not connected upstream Expansion or Expansion Ok 4 flashes Error 4 Not currently used Ok 5 flashes Error 5 Not currently used Ok 6 flashes Error 6 Not currently used Connecting the Paxton BLU Expansion Controller Wire the components to the Paxton BLU Expansion Controller as shown on page 4 Po...

Страница 6: ...pear as a single site The Master unit connects to Expansion units through a dedicated RS485 connection Each cable section between Master and Expansion and between Expansion and Expansion has its own section of cable carrying the half duplex RS485 communication between units Termination of the 485 data bus is done automatically by each Master and Expansion controller eliminating the need for field ...

Страница 7: ...ttach the interface adapter Please do so carefully and be sure that the PCB is fully secured to the bracket upon completion of the firmware update process CAUTION Make sure the adapter is plugged into both rows of the header on the PCB before you proceed see image below for proper placement and connection Power up the controller with the installer tool adapter installed Note your PC or laptop may ...

Страница 8: ...firmware update will take a minute once the green bar has progressed to fill the space the update is complete You can check the version of firmware installed using the View Device Detail option described in the previous section Tip It is useful to know which version of firmware is installed whenever you contact Technical Support Tip Remember to always download the latest version of the installer t...

Страница 9: ...ture Battery limits 0 C 32 F 55 C 131 F Weatherproof No Communication RS485 network speed 115 2 kbits sec RS485 Dataline 3280 84 ft 100m between controllers Features Number of Cards 100 000 Number of PINs 100 000 Access levels per customer 1000 Time zones 512 Door open time 1 sec 99 999 sec Data lines per system unlimited Doors per controller 2 Reader ports per controller 2 Readers Keypads per por...

Страница 10: ...10 Events stored in controller with no server connection 200 000 Dimensions Controller 4 1 64 inch W 4 3 4 inch H 1 inch D Cabinet 9 1 4 inch W 12 1 2 inch H 3 1 8 inch D ...

Страница 11: ...11 ...

Страница 12: ...18 08 2017 Paxton Ltd Ins 60006 GD US Managed access controller Expansion 837 520 US 838 621 US 1 0 3 Made in the UK ...

Отзывы: