A Nano must first bind to a Net2Air bridge before it will enroll itself onto the Net2 system. The term 'bind' is used 

to denote the fixed relationship between a Nano and its bridge.

Create a user record in the database and assign a Net2 token to the user.  If you are not using PROXIMITY tokens 

you should still create the user record and assign a token number (Not a PIN) of your choice.  These records can 

be deleted after the installation is complete.

Connect a PROXIMITY reader to the Nano and then present the same user token previously assigned.  (If you are 

enrolling a Keypad only unit, enter the token number on the keypad followed by  * )  The Nano will then transmit 

the token number and wait for a response from a bridge.

If more than one bridge replies, the Nano checks the signal strength and selects the strongest bridge to 

communicate with.  The Net2 software confirms that the token number is in the database and if so registers this 

Net2 nano/bridge binding.

Enrolling a Net2 nano

Software configuration

Reader

:  Settings for the Reader and Keypad.

Outputs

:  Lock,  Relay,  Alarm.  -  Selects these outputs to be 

used by the Lock, Bell or Alarm functions.

Alarm

: Configures the settings for the different alarm types.

Codes

:  Valid  keypad  codes  can  be  viewed,  added  and  removed                 

(This tab is only displayed when a keypad is fitted)

Events

: Shows the events for this control unit only.

Access Rights

:  Lists users who have access through this door.

Name

: Each reader can be named individually if required.

Reader type

: Set the reader type, if applicable.

Keypad type

: Set the keypad type, if applicable

Reader operating mode

: Set the operating mode.

Timed operating modes

: A different operating 

mode can be configured within a time window.

Door name

: Name the Door.

Door open time

: Set the door open time.

Unlock the Door during

: Holds the door unlocked during this 

timezone. - Set to  'At No Time'  for normal user operation.

Present a token at each reader. An event for each read should appear in the Events screen.

Change the default password for the System Engineer.

Set up other operators if required.

Set up time zones.

Set up access levels.

Users can be added & assigned to the required access level.

Departments can be created if required.

The Net2 CD can assist here with detailed application notes for setting up users and general system operation.

System checks 

UL compatable readers

Part

Type

373-110-US PROXIMITY P75 reader
373-120-US PROXIMITY P75 reader, screw connector
353-110-US PROXIMITY P50 reader
390-747-US PROXIMITY metal reader
390-727-US PROXIMITY metal reader, chrome
390-737-US PROXIMITY metal reader, brass
390-135-US PROXIMITY panel mount reader

Part

Type

371-110-US TOUCHLOCK K75 keypad
371-120-US TOUCHLOCK K75 keypad, screw connector
372-110-US TOUCHLOCK K75 stainless steel keypad
372-120-US TOUCHLOCK K75 stainless steel, screw connector
375-110-US PROXIMITY KP75 keypad
375-120-US PROXIMITY KP75 keypad, screw connector

Содержание 654-549-US

Страница 1: ...n contacts are closed Contact Orange The door contacts are closed Tamper Orange The tamper contacts are closed PSU Orange The PSU contacts are closed Net2Air Blue Net2Air interface Tx Rx activity OK Green flash The internal software is running LED indications This access control unit uses wireless communication It is recommended that a Net2Air site surveyor is used to determine the best position f...

Страница 2: ...r wireless communication There is NO Net2 nano detection function It is recognised that there could be security issues if the wireless units were detectable from outside the site During installation a Nano unit binds with a Net2Air bridge which will then only talk to registered units The Server configuration utility also has an Enable commissioning mode which can be turned off to inhibit Nano unit...

Страница 3: ...d the PC is updated when it comes back on line The ACU shall be installed within the protected premises as both the power and lock wiring is present at the PCB A Tamper alarm input is provided on the PCB See Input Output Wiring Where the ACU is being installed within a plastic enclosure the hub must be connected to the conduit before it is connected to the plastic enclose This is to eliminate the ...

Страница 4: ...Air bridge unit and also from the website as follows Software installation XAN1051 Installing Net2 software http paxton info 1520 XIns 40084 US Net2Air USB bridge http paxton info 1453 XIns 40085 US Net2Air Ethernet bridge http paxton info 1192 Only ONE Net2Air USB bridge may be used per system Multiple Net2Air Ethernet bridges may also be configured ...

Страница 5: ...control unit only Access Rights Lists users who have access through this door Name Each reader can be named individually if required Reader type Set the reader type if applicable Keypad type Set the keypad type if applicable Reader operating mode Set the operating mode Timed operating modes A different operating mode can be configured within a time window Door name Name the Door Door open time Set...

Страница 6: ...xternal devices Alarm output This is a transistor driven output that switches to 0V when activated The Net2 nano has 3 outputs that can be configured in the Doors screen to perform different functions This flexibility means that a site that requires the Relay output volt free contacts for the door function can configure the Lock output to drive a door bell Net2 nano reset The Nano controller holds...

Страница 7: ...Wiring Relay output Fail open 12V DC power supply Door lock Lock power supply Fail closed Lock with an independent supply ALARM 12V 12V Lock 0V 0V N C N O COM 0V y a l e R k c o L s t u p t u O r e w o P See Specification table for Output ratings Lock wiring Lock output 12V DC See Specification table for Output ratings This wiring illustration shows the Relay output configured for the Door lock fu...

Страница 8: ... an Alarm in the event of a Tamper condition The Net2 software will monitor the relay contacts and will raise an Alarm in the event of a Power Fail condition Door Bell Relay output Pressing the bell button on the keypad will energise the Door bell output for 1 second The Lock output Relay output or Alarm output must be configured to function as the Door Bell output This wiring illustration shows t...

Страница 9: ...oduct compliance and limitations To comply as a UL listed installation the following conditions must apply Server based functions Antipassback Time and Attendance etc have not been evaluated by UL and cannot be used for UL 294 installations The use of Wiegand readers and the configuration software has not been evaluated by UL Wiring Where an equivalent cable wire is used it must be UL Listed All i...

Страница 10: ...s range to ACU Dedicated lock output current Carrier frequency 60 days Reader port voltage Alarm output voltage Humidity Exit button voltage Exit button current Dedicated lock output voltage This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received ...

Отзывы: