23 Connection to Building Management System
62
99E13331xx-mub-en - V08
2022/07
23
Connection to Building Management System
The connection to the Building Management System (BMS) can be realised for an individual
domestic hot water module as well as for cascade operation (up to 4 single modules). The BMS
connection is carried out via the Modbus interface of the controller (single domestic hot water
module) or the Modbus RTU module MB3.10 (in the following abbreviated MB3.10) for Friwa
Cascade. For the data exchange between the participants of the bus, the Modbus RTU protocol
is used.
23.1
Single domestic hot water module
Connection of the controller to BMS
The domestic hot water modules with the FC3.10 controller have the great advantage that the
Modbus interface already exists at the controller. No additional hardware is required to realise
the BMS connection. Please use the PAW original communication cable RJ10 (item no.
N00317) to connect the FC3.10 controller to the BMS.
Insert one plug of the cable into the RS-485 port of the FC3.10 controller.
Use the other plug for the BMS connection.
If the connection to the BMS is
meant to be realised via a
clamping connection, please
consider the pin assignment of the
communication cable.