Model 6081RC blades installation
23
Model 6081RC Network Access Server User Manual
2 • Hardware installation
To install the Ethernet Access Module in your Model 6081RC, do the following:
1.
Set the Model 6081RC on a flat anti-static surface with the circuitry facing upward.
2.
Remove the PMC slot 2 protective cover from the Model 6081RC front panel (see
3.
Insert the front panel of the PMC card into the cutout for PMC slot 2 on the front panel of the Model
6081RC.
4.
Align the two connectors on the PMC card with the corresonding connectors on the Model 6081RC (see
5.
Gently and firmly press down on the rear of the PMC card, so that the connectors mate and snap
into place.
6.
Install the 4 fastening screws as shown in
on page 22. Gently tighten the screws into place.
Model 6081RC blades installation
The Model 6081RC installs in a Patton ForeFront chassis. The 6081RC is hot-swappable so it is not necessary
to power down the chassis before installing the blade.
Note
Verify that the rack chassis is properly grounded before installing the
Model 6081RC blades. An adequate ground can be achieved by con-
necting a #10 AWG ground wire between the rack chassis grounding
stud and one of the following ground sources:
You must wear the anti-static strap to avoid electrostatic damage
to the 6081RC or to the PMC Ethernet Access Module.
The 6081RC must not be installed in the chassis when installing
the PMC Ethernet Access Module.
The PMC Ethernet Access Module must be installed in PMC
slot 2. Do not install it in PMC slot 1.
Do not work on the system or connect or disconnect cables during periods of
lightning activity.
Ultimate disposal of this equipment must be handled according
to all applicable national laws and regulations.
CAUTION
CAUTION
CAUTION
WARNING
CAUTION