pass & seymour CS500 Скачать руководство пользователя страница 1

Syracuse, NY 13221

800.223.4185

Ins

tallation

Ins

tructions

CS Series

360° PIR Occupancy Sensor

Specifications

Voltages . . . . . . . . . . . . . . . . . . . . .20–30VDC (24VDC Typical)
Current Consumption . . . . . . . . . . .@24VDC, 11mA Maximum
Time Adjustment . . . . . . . . . . . . . . . . .15 seconds–30 minutes
Sensitivity Adjustment . . . . . . . . . . . . . . .Minimum/Maximum

U.S. Patents:

4,757,204 • 4,787,722

Des360,842

Содержание CS500

Страница 1: ...ructions CS Series 360 PIR Occupancy Sensor Specifications Voltages 20 30VDC 24VDC Typical Current Consumption 24VDC 11mA Maximum Time Adjustment 15 seconds 30 minutes Sensitivity Adjustment Minimum Maximum U S Patents 4 757 204 4 787 722 Des360 842 ...

Страница 2: ... of 360 The sensor has two lens pattern options The Extended Range Lens will cover up to 1200 sq ft and 22 feet from the sensor when mounted at 8 feet The High Density Reduced Range Lens will cover up to 500 sq ft and 12 feet from the sensor when mounted at 8 feet Coverage shown in the diagrams below is maximum and represents coverage for half step walking motion with no barriers or obstacles DRAW...

Страница 3: ... the mounting height you will decrease the range and increase the sensitivity to smaller motions Conversely when you increase the height you will increase the range and decrease the sensitivity to smaller motions At heights of more than 12 14 feet you may start to significantly reduce sensitivity Often the best location to install a CS sensor in a closed office is off center see fig 1 Avoid placin...

Страница 4: ...t about 2 3 4 to 3 in diameter 3 mud ring cut the hole to accommodate To assemble the sensor 1 If using the ceiling attachment ring bend the securing straps up so the sensor housing can be inserted and attach it to the sensor with the provided screws 2 Attach the mask if using into the lens recess and onto the securing pins of the cover 3 Attach the cover to the rear housing align tabs on inside o...

Страница 5: ...cover turns as it locks into position Note At the edges of the masking there is a small area of reduced sensitivity illustrated as the lighter area in the examples below WIRING DIRECTIONS CAUTION TURN POWER OFF AT CIRCUIT BREAKER BEFORE WIRING SENSOR Pass Seymour PWP2 series power packs supply power for up to 10 CS Sensors When using more sensors than this multiple power packs are required To conn...

Страница 6: ...hould go off after 15 seconds Note If lights remain on move farther away or out of sight of the sensor If lights still remain on set the Sensitivity to medium high by setting DIP switches 7 to ON and 8 to OFF or see Unwanted Sensor Activations under Troubleshooting 6 Set the appropriate Time Delay DIP switches 1 through 6 The factory preset Time Delay is 18 minutes other suggestions are Offices an...

Страница 7: ...um and allow the sensor to time out If the lights turn off the sensor is working correctly See Unwanted Sensor Activations below Go through the Sensor Adjustment process again If the lights stay on the problem may be in the power pack See Power Pack High Voltage Checklist below Power Pack High Voltage Checklist CAUTION Use proper high voltage precautions 1 Check that power pack high voltage wire c...

Страница 8: ...TIAL DAMAGES FOR BREACH OF ANY AND ALL EXPRESSED OR IMPLIED WARRANTIES INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE EXCLUDED HEREBY Some states do not allow disclaimer or exclusion or limitation of incidental or consequential damages so the above disclaimers and limitation or exclusion may not apply to you ANY IMPLIED WARRANTIES INCLUDING WHERE REQUIRED WARRANTIE...

Отзывы: