26
Cantinola Touch 2016 operating and maintenance manual
DISTANCES TO STRICTLY FOLLOW IN THE ROOM OF INSTALLATION
Objects which could cause fires must not be put in contact or near the boiler.
The boiler is not designed for a build-in installation, so the following distances are only to be
considered as safety distances from objects which could cause a fire and not as minimum
sizes of a housing to recess the stove.
In case of wooden floors or floors made of flammable materials (carpeted floors, etc.) a guard
made of non-flammable materials must be fitted (reaction to fire class 0). It should cover the
floor area in front of the stove
The minimum distances from the boiler are as follows:
300 mm from the rear
300 mm from the side
300 mm from the ceiling
30 mm from the floor
1000 mm from the front
In case the walls next to the boiler (e.g. the
rear wall) are made of flammable materials (like wood), a protection a fire-resistant covering
must be fitted.
THE CHIMNEY
GENERAL FEATURES
The Pellet Boiler has forced draught, so it is not possible to use a common multiple
chimney. Combustion fumes are sucked by the extraction fan, which also takes
combustion air in. The function of the extraction fan is functional according to a
proper combustion air and smoke extraction, so to ensure a successful evacuation
of smokes outside the home. An efficient chimney and good natural draft will be
much helpful to ensure an appropriate depression for a better operating