2.1.3. Loop detector configuration & testing:
Loop detector setting verification:
Sensitivity:
Default=A
(0,1,2…8,9,A...EF; Low -> High; Rotary switch)
Dip switch setting:
DIP
No.
LOOP1
Default
LOOP2
Default
Description
1
OFF
OFF
ON=2 seconds delay; OFF= No delay.
2
OFF
OFF
Automatic sensitivity boost ON/OFF
3
OFF
OFF
Output B pulse on entry = (DIP3=OFF, DIP4=OFF)
Output B presence = (DIP3=OFF, DIP4=ON)
Output B pulse on exit = (DIP3=ON, DIP4=OFF)
4
ON
ON
5
ON
ON
ON=Infinite presence; OFF=Normal presence.
6
OFF
OFF
No extend=(DIP6=OFF, DIP7=OFF, DIP8=OFF)
Extend 2 SEC=(DIP6=ON, DIP7=OFF, DIP8=OFF)
Extend 5 SEC=(DIP6=OFF, DIP7=ON, DIP8=OFF)
Extend 8 SEC=(DIP6=ON, DIP7=ON, DIP8=OFF)
Extend 10 SEC=(DIP6=OFF, DIP7=OFF, DIP8=ON)
Extend 15 SEC=(DIP6=ON, DIP7=OFF, DIP8=ON)
Extend 20 SEC=(DIP6=OFF, DIP7=ON, DIP8=ON)
Extend 30 SEC=(DIP6=ON, DIP7=ON, DIP8=ON)
7
OFF
OFF
8
OFF
OFF
9
OFF
ON
LOW frequency=(DIP9=ON, DIP10=ON)
MED LOW frequency=(DIP9=OFF, DIP10=ON)
MED HIGH frequency=(DIP9=ON, DIP10=OFF)
HIGH frequency=(DIP9=OFF, DIP10=OFF)
10
OFF
ON
Loop wiring condition verification:
Press “RESET” button on the loop detector and check the DETECT and POWER LEDs:
POWER LED (red color) light should be on, if not, check AC power source and fuse
(0.5A, inside of the detector).
DETECT LED (green color) light should be either on (detected status) or off (no
detection status):
If blinking, check the loop wiring for a short circuit first.
If blinking very slowly, loop wiring does not have enough turns. Add extra loop turns
until DETECT LED light is not blinking.
If blinking very rapidly, loop wiring has too many turns. Remove loop turns until
DETECT LED light is not blinking.
Note
:
Setup diff. frequency for nearby detectors