Bulletin MSG11-40983307/UK

ValveMaster

®

 Test Unit

Operation Manual

Series EX-M05

Parker Hannifin 
Manufacturing Germany GmbH & Co. KG

Industrial Systems Division Europe
Gutenbergstr. 38
41564 Kaarst, Germany
E-mail: [email protected]
Copyright © 2019, Parker Hannifin Corp.

Содержание ValveMaster EX-M05 Series

Страница 1: ...Master Test Unit Operation Manual Series EX M05 Parker Hannifin Manufacturing Germany GmbH Co KG Industrial Systems Division Europe Gutenbergstr 38 41564 Kaarst Germany E mail valvesisde parker com Copyright 2019 Parker Hannifin Corp ...

Страница 2: ...tem and components and assuring that all performance endurance maintenance safety and warning requirements of the application are met The user must analyze all aspects of the application follow applicable industry standards and follow the information concerning the product in the current product catalog and in any other materials provided from Parker or its subsidiaries or authorized distributors ...

Страница 3: ... Technical features 4 Ordering code 4 Technical data 4 Overview control panel 5 Overview backside 5 Connecting configuration 6 Functional description 7 Command values 7 Operation DC on off valve 7 Measurement selection 8 Diagnostic signal selection pin F 8 Enable signal 8 Acknowledgement on fault condition 8 External measuring device 8 ...

Страница 4: ... code Design series Test unit Design Lockable rugged box polypropylene break proof Supply voltage V 85 260 50 60 Hz Power consumption VA max 160 Current consumption max A 1 3 at 230 V Main input fuse A 3 15 time lag Required main supply fuse A 16 Protection class IP40 EMC EN 61000 6 2 Valve central connection Valve supply V 24 5 Command voltage V 0 10 1 0 10 0 20 mA 0 20 mA 4 12 20 mA 4 20 mA Diag...

Страница 5: ...ange indicator 12 Diagnostics terminal 13 Command range selector 14 Diagnostic mode selector pin F V mA 1 Command value 1 2 Command value 2 3 Zero position failure acknowledgement 4 Potentiometer command value 1 5 Potentiometer command value 2 6 Enable 7 Diagnostics pin selection A C D F 8 DC valve on off 15 17 16 18 19 15 Valve connector 7 pin 24 VDC 16 DC valve connector 5 pin 24 VDC limited to ...

Страница 6: ...260 V 50 60 Hz G U I Terminal Value unit Terminal Selection 0 10V 0 20mA 4 20mA 10 0 10V 20 0 20mA 4 12 20mA Diagnostics Terminal VS 0V CMD 0V A B C D E F G CMD Mode intern extern Diagn Mode 10V 20mA Enable CMD Zero CMD 2 CMD 1 OB OFF Valve 24VDC max 40W OFF ON G A B C D E F G external command signal See valve manual for pin assignment ...

Страница 7: ...command range 4 12 20 mA it is 12 mA in the command range 10 0 10 V it is 0 V and in the command range 4 20 mA it is 4 mA By pressing a corresponding command button 1 2 the previously set command value is availa ble on Pin D E of the valve plug It is still possible to change both command values via the potenti ometers 4 5 Pressing the CMD Zero button 3 brings the valve back to zero position Extern...

Страница 8: ...a tion which is switched on or off by pushing the En able button 6 The button lighting indicates the status Enable active LED on Enable off LED off If there is a faulty connection to the C pin the enable signal will be automatically switched off blocked or the current flow will be limited to 5mA depending on the type of signal This will prevent damage to the electronics of valve and or testing uni...