PARKER Accumulator & Cooler Division  

15102 Sommermeyer, Suite 125, Houston, Texas, 77041     Tel. (713) 937-8900  Fax: (713) 937-0438 

Installation and Servicing Instructions: 
ULAC Air/Oil Cooler 

 
These instructions should be strictly observed prior to 
installation of the  PARKER ULAC cooler. 
 

Mounting 

The ULAC air oil cooler permits both suspended and foot 
mounting.  To prevent personal injury, always secure the 
cooler adequately.  The distance from the nearest wall should 
not be less than half the height of the cooler core. 
 
 

 

 
 
 

Hydraulic connection 

Connect the cooler as illustrated below using hydraulic hoses 
both to and from the cooler.  We recommend mounting in a 
separate cooling circuit; In case this is not possible, install the 
cooler in the system return line.  Avoid linking to systems that 
could yield in pressure spikes greater than 200 psi.  PARKER 
shall not be liable for the consequences of any modification 
and/or variation with regards to connections. 
 
 

 

 
Electrical connection 

 

Danger 230/460V! 

Installation should only be performed by a 

qualified electrician.

 

 

Prior to start-up 

 

Check the cooler core and fan guard for damages 

 

Check that the cooler is correctly connected according to 
the above.  PARKER shall not be liable for the 
consequences of any variation. 

 

Manually turn fan to be sure it does not hit fan housing. 

 

Check that the cooler is provided with a caution label for 
rotating fan. 

 

At start-up 

 

Check that the fan’s direction of rotation is correct, i.e. 
that the electric motor poles are correctly connected. 

 

Noise level 

Remaining in close proximity to the cooler for an extended 
period might be annoying.  Inappropriate placement of the 
cooler, e.g. on a large flat sheet, could give rise to a high noise 
level.  Contact PARKER for advice.

 

 
Cleaning the cooler core 

The easiest way to clean the air fins of the core is by using 
compressed air.  Fouling can be dealt with using a high-
pressure washing system and a degreasing agent.  Flush with 
water afterwards. 
 
Caution: When using a high-pressure washing system, point 
the jet parallel to the air fins.  The cooler core should be cool 
before cleaning. 
 
To clean the inside of the core, connect the core to a closed 
circuit and flush the inside with degreasing agent.  After 
cleaning, the core should be flushed with the same fluid as 
used in the system itself. 
 

 
 
 
 