Page 98
– Bulletin 100-50-9.1
11.3 CASE LEVEL CONFIGURATION
The case level menu can be used to view and change case
parameters. It may be used for troubleshooting or updating
parameters.
To access Case Level Menus:
1. From the
default
display, press the
button. The
display will show
.
2. Use the
▲▼
buttons to enter the
administrator
password and press
SET.
3. The display will show
; press
SET.
4. Use the
▲▼
buttons to select the desired parameter, see
Table 8 below.
5. Press the
SET
button to enter and change the
parameter.
6. After adjusting the parameter, press the
SET
button to
commit the change.
11.4 BASIC OPERATIONAL CONFIGURATION
The basic menu presents key case parameters that may be
changed. If entering this menu thru the Administration
level password, changes will be permanent. Use caution
when changing parameters from the original OEM settings.
To access Basic Parameter Menu:
7. From the
default
display, press the
button. The
display will show
.
8. Use the
▲▼
buttons to enter the
administrator
password and press
SET.
9. The display will show
; press
SET.
10. Press the
▲
button to scroll to the basic menu
;
press
SET.
11. Use the
▲▼
buttons to select the desired parameter.
12. Press the
SET
button to enter and change the
parameter.
TABLE 6 - TOP LEVEL MENUS
Display
Meaning
Description
Hide Condition
Case Configuration
Allows configuration of case level parameters
e
Line-up Configuration
Allows viewing of line-up level process values
(1)
3
Evaporator 3
Configuration
Allows configuration of evaporator level sensors offsets for evaporator 3
(2)
2
Evaporator 2
Configuration
Allows configuration of evaporator level sensors offsets for evaporator 2
(3)
TABLE 7 - HIDE CONDITIONS FOR TOP LEVEL MENU ITEMS
Number
Hide Condition
1
Case type is self-contained
2
e
Number of evaporators is configured to < 3
3
e
Number of evaporators is configured to 1
TABLE 8 - CASE CONFIGURATION MENUS
Display
Meaning
Description
Process values
Allows viewing of operational and sensed values
Basic operational configuration
Configuration of basic operational settings
Valve configuration
Configuration of attached valves
Sensor configuration
Configures type, range, offset and use of sensors
User alarm configuration
Configures user alarm thresholds and delays
d
Display (DM) configuration
Configures passwords, display actions and units
Lighting control configuration
Configures lighting schedule and occupancy sensor action
def
Defrost configuration
Configures defrost type and settings
f
Evaporator fan control configuration
Configures evaporator fan settings and alarms
Anti-sweat heater control configuration
Configures anti-sweat heater control
d
Case controller indentifier configuration
Indentifies case location based on rack and line-up ID
e
Network configuration
Configures network for BAS and peer - peer
de
Set time and date
Used for setting internal real time clock (RTC)