- 20 - 

Display 

Function Description 

Setup Options and Descriptions 

Factory 

Setting 

Remarks 

C-06 

Flow rate output voltage 
range selection (analog 

PV

 output range 

selection) 

0: 

0 to 5 Vdc output 

1: 

1 to 5 Vdc output 

 

C-07 

Event output 1 type 
assignment 

C-08 

Event output 2 type 
assignment 

0: 

Not used (OFF at all times) 

1: 

ON when alarm activated 

2: 

Totalization pulse output 

3: 

On when 

PV

 is in flow rate OK 

judgment range 

4: 

ON in control mode 

5: 

ON in fully open mode 

6: 

ON in control mode or fully open 
mode 

7: 

ON in fully closed mode 

8: 

Instantaneous 

PV

 upper limit event 

9: 

Instantaneous 

PV

 lower limit event 

10: 

Instantaneous 

PV

 lower limit event 

11: 

Integrated flow rate event 

-1 through -11:  Reverse output of 1 to 11 

(At no events: ON; at 
event occurred: OFF) 

Flow rate OK judgment range, upper/lower limit 
event flow rate, totalized event flow rate and 
event output delay time are set in the parameter 
setup mode.  See “Parameter Setup” for details.  
Note the delay time cannot be set to totalization 
pulse output. 

 

 

 

 

 

 

9: 

Events are output even in fully closed 
operation mode. 

10: 

Events are not output in fully closed 
operation mode. 

 

-1 through -11:  Always OFF during power supply 

OFF. 

C-10 

External switch input 1 
function assignment 

C-11 

External switch input 2 
function assignment 

0: 

Not used 

1: 

Reset totalization 

2: 

Stop totalization count operation 

3: 

Switching of 

SP

 number 

4: 

Switching of flow rate setup method 

5: 

Valve fully closed 

6: 

Valve fully open 

7: 

Switching of slow start operation 

8: 

Switching of operating mode: 

Contact ON: control mode 

Contact OFF: fully closed mode 

3: 

To select three (3) or more 

SP 

settings, 

assign “3” to both ‘

C–10

’ and ‘

C–11

’. 

4: 

The ‘

C-03

’ (analog/digital) setting is 

reversed when the contact is ON. 

7: 

“Slow start enabled” must be selected in ‘

C-

17

’. 

5, 6, 8:  When the valve fully closed input and the 

valve fully open input are put in at the 
same time by two contacts, the both 
inputs are disabled. 

C-13 

Valve automatic shut-off 
when the totalization 
event occurred 

0: 

Function disabled 

1: 

Function enabled 

When the totalized count value reaches the 
totalized event setting value, the valve is fully 
closed. 

C-14 

Resetting the totalized 
value at start of control 

0: 

Function disabled 

1: 

Function enabled 

When control is resumed from the fully closed 
mode, the totalized value is automatically reset. 

C-15 

Flow rate alarm setup 
type 

0: 

Not used 

1: 

Only upper limit alarm used 

2: 

Only lower limit alarm used 

3: 

Upper/lower limit alarm used 

Set the alarm flow rate in the parameter setup 
mode.  See “Parameter Setup” for details. 

FUNCTION SETUP ITEM LIST (continued) 

Содержание Porter MPC Series

Страница 1: ...MPC SERIES PANEL MOUNT MASS FLOW CONTROLLER INSTALLATION PROGRAMMING USER S MANUAL FM 1038 Rev 0 4 08...

Страница 2: ...G 9 Location 9 Dimensional Data 9 Mounting Procedure 9 External Electrical Connections 11 Section 5 BASIC OPERATION 13 Switching Displays 13 Setting the Flow Rate 15 Selecting the Operation Mode 17 Se...

Страница 3: ...positive shut off is a system requirement install a separate shut off valve When a separate shut off valve is closed the user must command the MFC control valve fully closed by one of the following me...

Страница 4: ...User s Manual FM 1032 One 1 FEATURES The MPC Series Panel Mount MFC is a mass flow controller featuring high performance in a compact package design Integrating the advanced technologies of an ultra...

Страница 5: ...rt stop reset can be remote controlled by external switching input After a reset by key operation the totalization calculation is started automatically However if a reset contact ON is carried out by...

Страница 6: ...parate shut off valve AUTOMATIC RESET OF TOTALIZATION COUNT AT START OF CONTROL FUNCTION Start of control and totalization count reset can be carried out simultaneously by a single action key operatio...

Страница 7: ...0 C 14 to 140 F Humidity Operating Humidity Range 10 to 90 Relative Humidity non condensing Setpoint Input Keypad Operation or External Setpoint Voltage Input Resolution Refer to Table 1 Setpoint Setp...

Страница 8: ...lectrical connector Note 1 SLPM indicates the volumetric flow corrected to 20 C and 1 atmosphere 14 7 PSIA The reference temperature can also be changed to 0 C 25 C and 35 C The controllable flow rang...

Страница 9: ...also displays the operation mode totalized flow rate value lower 4 digits valve drive output parameter setup values or function setup values OPERATION LAMP L Indicates the totalized flow rate is disp...

Страница 10: ...nnection of a dedicated loader cable available separately to the loader jack on the rear of the MFC enables direct communication with a personal computer IN CONNECTOR 1 8 FNPT inlet connector OUT CONN...

Страница 11: ...NG PROCEDURE PROCESS CONNECTION INSTALLATION While installing the inlet and outlet process connections to the inlet and outlet 1 8 FNPT connectors do not hold the housing of the MPC Series Panel Mount...

Страница 12: ...From the front of the panel insert the MFC through the panel cutout until the MFC s bezel rests against the front of the panel With the mounting bracket screws oriented vertically i e 6 o clock and 12...

Страница 13: ...ng power The event output does not exceed the specified output rating of the MFC When driving a relay use a relay with a built in diode for coil surge suppression ELECTRICAL CONNECTOR SPECIFICATIONS P...

Страница 14: ...12 WIRING TYPICAL WIRING...

Страница 15: ...e function setup For details on function setup method refer to SECTION 6 APPLICATION OPERATION 5 If no setting change is made while the multi setting flow rate is displayed the display will automatica...

Страница 16: ...OW RATE DISPLAY When the DISP key is pressed while the operation mode is displayed the L lamp lights and the totalized flow rate value is indicated on the upper display and lower display For example i...

Страница 17: ...when performing incremental changes to the SP value Multi SP Setpoint Setting Mode Multiple Setpoints Per Function Setup C 04 Up to four 4 SP setpoint values setting flow rate values can be programme...

Страница 18: ...splayed indication is automatically returned to the instantaneous flow rate display PROCEDURE FOR CHANGING FLOW RATE IN ANALOG SETTING To change the SP value using an external setpoint voltage confirm...

Страница 19: ...the DISP key is pressed 3 When the DISP key is pressed while the display is flashing step 2 of Selecting the Operating Mode procedure above the operating mode selection is cancelled 4 When 5 Valve ful...

Страница 20: ...onds or longer press DISP key less than 1 second press DISP key or any key is not pressed for 10 seconds or longer press DISP key 1 second or longer flow rate indication 3 Totalized flow rate Totalize...

Страница 21: ...ow rate display FUNCTION SETUP ITEM LIST Display Function Description Setup Options and Descriptions Factory Setting Remarks C 01 Key lock 0 Unlocked 1 Settings other than flow rate setting are locked...

Страница 22: ...nal switch input 1 function assignment 0 C 11 External switch input 2 function assignment 0 Not used 1 Reset totalization 2 Stop totalization count operation 3 Switching of SP number 4 Switching of fl...

Страница 23: ...pressure adjustment 0 0 0 1 MPa 0 14 5 PSIG 1 0 05 0 15 MPa 7 25 21 8 PSIG 2 0 15 0 25 MPa 21 8 36 3 PSIG 3 0 25 0 35 MPa 36 3 50 8 PSIG 4 0 35 0 45 MPa 50 8 65 3 PSIG 5 0 45 0 5 MPa 65 3 72 5 PSIG 2...

Страница 24: ...ence No Display Parameter Description Factory Setting Setting Range Refer to Function Setup Item Remarks 1 0 r 9 1 Flow rate OK judgment range 2 FS 10 0 5 to 100 FS 10 2 0 HYS 1 Flow rate OK judgment...

Страница 25: ...vent output type assignment in the function setup 7 This can be set only when 1 Function enabled is selected for the C 28 analog optional scaling function in the function setup 8 This can be set only...

Страница 26: ...the gas is shut off for more than five 5 minutes set the set flow rate SP to zero or valve fully closed AL81 Sensor error Sensor problem particulate in sensor or use of helium or hydrogen gas Turn po...

Страница 27: ...nstall an upstream filter Contact factory Flow rate does not stabilize Operational differential pressure range is exceeded Excessive supply pressure fluctuations Pressure regulator compatibility Exces...

Страница 28: ...ter Instrument Division and accompanied by a properly completed Returned Goods Authorization All returns are subject to restocking and possible rework charges to be determined by Porter Instrument Div...

Страница 29: ...ons and calibration the customer will be notified of the costs before proceeding with repair or replacement Repaired equipment will be warranted ninety 90 days from date of delivery to the customer or...

Страница 30: ......

Отзывы: