Parker Hannifin Corporation
Pneumatic Division Europe
www.parker.com/pde
48
Integration Guide
Siemens Simatic S7
FRL-SIF-120
_EU
Parker Pneumatic
Siemens Wiring Schematic Safe Output with Sensor Test Pulse to Interface to
Safety Exhaust Valve
With this schematic it is possible to achieve up to category 4 PL e if properly implemented.
External monitoring program for Siemens Simatic S7*
a) If Dia.0 = Dib.0 = 1 AND safety hardwire circuit in Active state AND no faults present THEN SET O0 = 1 when
commanded
b) Sensor discrepancy error: Dia.0 <> Dib.0 (max. discrepancy time = 150 msec)
c) Loss of pressure error: O0 = 1 AND Dia.0 = Dib.0 = 0
followed by Dia.0 OR Dib.0 AND O0 = 1
d) System pressure error: O0 = 1 AND Dia.0 = Dib.0 = 1 for x amount of time (where x is system pressurization
time dependent on volume) Default 3 secs.
e) IF sensor discrepancy error OR loss of pressure error OR system pressure error THEN reset O0 = 0
Errors must be reset only after maintenance acknowledgement
* Programs provided in this integration guide are for reference only. These programs have not been certified or tested
unless stated otherwise.
1 Brown
2 White
3 Blue
4 Black
5 Grey
5
1
3
4
2
Sol 1 Sol 2
C
+
-
5
1
3
4
2
C
+
+
-
SW
1
SW
2
M12 Pinouts for P33
+ 24V
0V -
B3 BLUE
B1 BROWN
B5 GREY
SW1
SW2
B2 WHITE
B4 BLACK
A4 BLACK
A3 BLUE
SOL 1
SOL 2
0V
24V
(P)
(M)
Vs1
Vs2
Dlb 0
Dla 0