Chapter 1. Installation
1 7
OUTPUT CONNECTIONS —
for electronic devices such as PLCs
Connection to a Sinking Input (active high)
Connection to a Sourcing Input (active low)
Electronic
Device
Output
Connection
Ground
Connection
Input
Ground
OUT-P
+5V
GND
AT6n00
7406
4.7 K
Ω
+5VDC
ISO GND
ISO GND
External Supply
(up to 24VDC)
+
–
(open collector)
Electronic
Device
Output
Connection
Ground
Connection
Input
Ground
OUT-P
+5V
GND
AT6n00
7406
4.7 K
Ω
+5VDC
ISO GND
ISO GND
External Supply
(up to 24VDC)
+
–
(open collector)
V+
Connection to a Combination of Sinking & Sourcing Inputs
Combinations of sourcing
and sinking inputs can be
accommodated at the same
voltage level. Be aware of
the input impedance of the
sourcing input module, and
make sure that there is
enough current flowing
through the input module
while in parallel with the
OUT-P pull-up resistor.
Electronic
Devices
Output 1
Input
Ground
OUT-P
+5V
GND
AT6n00
7406
4.7 K
Ω
+5VDC
ISO GND
External Supply
(up to 24VDC)
+
–
(open collector)
V+
Output 2
Ground
Connection
Input
Ground
7406
4.7 K
Ω
ISO GND
(open collector)
Sourcing Input
Sinking Input
Connection to an Inductive Load (active low)
Output
Connection
OUT-P
+5V
GND
AT6n00
7406
4.7 K
Ω
+5VDC
ISO GND
External Supply
(up to 24VDC)
+
–
(open collector)
Use an external diode when driving
inductive loads. Connect the diode
in parallel to the inductive load,
attaching the anode to the AT6n00
output and the cathode to the
supply voltage of the inductive load.
PROGRAMMING TIP
Connecting to an active-
high sinking input? Set
the output's active level to
high with the
OUTLVL
command
(
1
= active high).
Connecting to an active-
low sourcing input? Set
the output's active level to low
with the
OUTLVL
command
(
Ø
= active low).
Thus, when the AT6n00's
output is activated, current will
flow through the attached
input and the
TOUT
status
command will report a “
1
”
(indicates that the output is
active), regardless of the type
of input that is connected.
Details on setting the active
level and checking the output
status are provided in the
6000 Series Programmer's
Guide. Refer also to the
OUTLVL
and
TOUT
command
descriptions in the
6000
Series Software Reference.
Содержание Compumotor AT6200
Страница 5: ......