2.7.2.
Conditions of utilization for cables / motor filter
Operation of the devices only with motor and feedback cables whose plugs
contain a special full surface area screening.
< 100 m (the cable should not be rolled up!)
A motor output filter is required for motor cables >20 m:
MDR01/04 (max. 6.3 A rated motor current)
MDR01/01 (max. 16 A rated motor current)
MDR01/02 (max. 30 A rated motor current)
Shielding connection of the motor cable
The cable must be fully-
screened and connected to the Compax3 housing. Use the
cable clamps/shield connecting terminals furnished with the device.
The shield of the cable must also be connected with the motor housing. The fixing
(via plug or screw in the terminal box) depends on the motor type.
< 100 m
Corresponding to the specifications of the terminal clamp with a temperature range
of up to 60°C.
Signal lines and power lines should be installed as far apart as possible.
Signal lines should never pass close to excessive sources of interference
(motors, transformers, contactors etc.).
Do not place mains filter output cable parallel to the load cable.
2.7.3.
Additional conditions of utilization
Operation with standard motors.
Use only with aligned controller (to avoid control loop oscillation).
Connect the filter housing and the device to the cabinet frame, making sure that the
contact area is adequate and that the connection has low resistance and low
inductance.
Never mount the filter housing and the device on paint-coated surfaces!
For CE and UL conform operation of the Compax3S300V4, a mains filter is
compulsory:
400 VAC / 0.740 mH certified in accordance with EN 61558-1 bzw. 61558-2-2
We offer the mains filter as an accessory: LIR01/01
Make sure to use only the accessories recommended by Parker
Connect all cable shields at both ends, ensuring large contact areas!
Motor and Feedback
cable:
Compax3S motor
cable
Compax3 encoder
cable:
Cable
Cable installation:
Motors:
Control:
Grounding: