26
CM2115
Inputs
Type 2 Analog Input Ranges - INPUT 15
GAIN
Max Volts
ATN1
ATN2
1.000 3.000 OFF
OFF
0.192 15.611 ON OFF
0.148 20.314 OFF ON
0.091 32.925 ON ON
Type 2 Analog Input Ranges - INPUT 11-14, 16
GAIN
Max Volts
ATN1
ATN2
1.000 3.000 OFF
OFF
0.542 5.535 ON OFF
0.223 13.423 OFF ON
0.188 15.958 ON ON
5.6.2. Analog Input Configurations
The analog inputs have the ability using software to have either a pull-up or pull-
down resistor enabled, have pull-up and pull-down enabled at same time, have a
separate pull-down (of 249 ohms) enabled for 4 to 20 mA current sensor, or no
pull-up or pull-down resistors at all.